B.9 n: Special Adjustment

The n parameters adjust more advanced performance characteristics such as Hunting Prevention, High Slip Braking, and

Overexcitation Braking.

u

n1: Hunting Prevention

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n1-01

(0580)

Hunting Prevention

Selection

Hunt Prev Select

0: Disabled

1: Enabled

V/f

V/f

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

n1-02

(0581)

Hunting Prevention

Gain Setting

Hunt Prev Gain

V/f

V/f

If the motor vibrates while lightly loaded, increase the gain by

0.1 until vibration ceases. If the motor stalls, decrease the gain

by 0.1 until the stalling ceases.

Default: 1.00

Min.: 0.00

Max.: 2.50

n1-03

(0582)

Hunting Prevention

Time Constant

Hunt Prev Time

V/f

V/f

Sets the time constant used for Hunting Prevention.

Default:

<1>

Min.: 0 ms

Max.: 500 ms

n1-05

(0530)

Hunting Prevention

Gain while in Reverse Hprev Gain @Rev

V/f

V/f

Sets the gain used for Hunting Prevention. If set to 0, the gain

set to n1-02 is used for operation in reverse.

Default: 0.00

Min.: 0.00

Max.: 2.50

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

n2: Speed Feedback Detection Control (AFR) Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n2-01

(0584)

Speed Feedback

Detection Control

(AFR) Gain

AFR Gain

OLV

OLV

OLV

OLV

Sets the internal speed feedback detection control gain in the

automatic frequency regulator (AFR).

If hunting occurs, increase the set value. If response is low,

decrease the set value.

Default: 1.00

Min.: 0.00

Max.: 10.00

n2-02

(0585)

Speed Feedback

Detection Control

(AFR) Time Constant

1

AFR Time

OLV

OLV

OLV

OLV

Sets the time constant used for speed feedback detection control

(AFR).

Default: 50 ms

Min.: 0

Max.: 2000

n2-03

(0586)

Speed Feedback

Detection Control

(AFR) Time Constant

2

AFR Time 2

OLV

OLV

OLV

OLV

Sets the AFR time constant to be used during Speed Search and

during regen.

Default: 750 ms

Min.: 0

Max.: 2000

u

n3: High Slip Braking (HSB) and Overexcitation Braking

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n3-01

(0588)

High-Slip Braking

Deceleration Frequency

Width

HSB DecStepWidth

V/f

V/f

Sets the output frequency reduction step width for when the

drive stops the motor using HSB. Set as a percentage of the

maximum output frequency. Increase this setting if overvoltage

occurs during HSB.

Default: 5%

Min.: 1

Max.: 20

n3-02

(0589)

High-Slip Braking

Current Limit

HSB Current Lim

V/f

V/f

Sets the current limit during HSB as a percentage of the motor

rated current.

Default:

<1>

Min.: 100%

Max.: 200%

n3-03

(058A)

High-Slip Braking

Dwell Time at Stop

HSB DwelTim@Stp

V/f

V/f

Sets the time the drive will run with minimum frequency

(E1-09) at the end of deceleration.

If this time is set too low, the machine inertia can cause the motor

to rotate slightly after HSB.

Default: 1.0 s

Min.: 0.0

Max.: 10.0

B.9 n: Special Adjustment

368