Flange type heat loss data – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 73
n
Flange Type Heat Loss Data
Table 2.17 Models 2A0069 and 2A0081, 4A0044, and 5A0027 and 5A0032
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
2A0069
200
204.5
491.3
695.8
162.8
394.9
557.7
9.1 (20.0)
2A0081
257.4
527.4
784.8
220.9
459.8
680.7
10.0 (22.0)
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
4A0044
400
208.9
389.6
598.5
179.4
329.8
509.2
8.7 (19.1)
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
5A0027
600
227.2
132.1
359.3
113.9
267.2
381.1
8.7 (19.1)
5A0032
279.9
141.6
421.5
132.2
332.9
465.1
8.7 (19.1)
2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss