b5-03

(01A7) Integral Time Setting (I) PID I Time

Sets the integral time for the PID controller.

Default: 3.0 s

Min.: 0.0

Max.: 360.0

215

b5-04

(01A8) Integral Limit Setting

PID I Limit

Sets the maximum output possible from the integrator as a

percentage of the maximum output frequency.

The function of b5-04 is disabled when P1-24 > 0

Default: 100.0%

Min.: 0.0

Max.: 100.0

b5-05

(01A9) Derivative Time (D)

PID D Time

Sets D control derivative time.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

b5-06

(01AA) PID Output Limit

PID Limit

Sets the maximum output possible from the entire PID controller

as a percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

b5-07

(01AB) PID Offset Adjustment PID Offset

Applies an offset to the PID controller output. Set as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

b5-08

(01AC) PID Primary Delay

Time Constant

PID Delay Time

Sets a low pass filter time constant on the output of the PID

controller.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

b5-09

(01AD)

PID Output Level

Selection

Output Level Sel

0: Direct Acting

1: Inverse Acting

0: Direct acting

1: Inverse acting

Default: 0

Range: 0, 1

215

b5-10

(01AE) PID Output Gain Setting Output Gain

Sets the gain applied to the PID output.

Note:

Parameter setting cannot be changed when the

drive is operating the motor in models 4A0930

and 4A1200.

Default: 1.00

Min.: 0.00

Max.: 25.00

b5-11

(01AF)

PID Output Reverse

Selection

Output Rev Sel

0: 0 limit

1: Reverse

0: Negative PID output triggers zero limit.

1: Rotation direction reverses with negative PID output.

Note:

When using setting 1, make sure reverse

operation is permitted by b1-04.

Default: 0

Range: 0, 1

b5-12

(01B0)

Feedback Loss 4 to 20

mA Detection Selection

Fdbk 4-20mA Det

0: Disabled

1: Alarm only

2: Fault

3: Run At b5-13

Performs a 4 to 20 mA wire break detection on the analog input

that is programmed for PID feedback.

0: Disabled

1: Alarm only

2: Fault

3: Run at b5-13

Default: 2

Range: 0 to 3

b5-13

(01B1)

Feedback Loss Goto

Frequency

FdbkLossGotoFreq

Sets the speed at which the drive will run if a 4 to 20 mA wire

break is detected on the PID Feedback and when b5-12 is set to

3 (Run at b5-13).

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b5-14

(01B2) Feedback Loss of Prime

Level

FdbkLoss LOP Lvl

Detects loss of prime in the pump when a wire break condition

has occurred.

When the measured quantity determined by P1-18 (output

current, kilowatts, or power) drops below this level for the time

set in P1-20 and the output frequency is at the level set in b5-13,

a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<1>

Min.: 0.0

Max.: 1000.0

b5-15

(01B3)

<2>

Feedback Loss Go To

Frequency Time Out

FdbkLossGotoTimO

When b5-12 = 3 and the Feedback signal is lost, the drive will

run at the b5-13 speed for the b5-15 time, after which the drive

will fault on Feedback Loss (FDBKL).

Timeout is disabled when set to 0sec and the drive will run

indefinitely at b5-13.

Default: 0 s

Min.: 0

Max.: 6000

b5-16

(01B3)

<2>

Feedback Loss Start

Delay

FdbkLossStartDly

When an AUTO Run command is initiated, the drive will not

fault on Feedback Loss (FDBKL) or use the Feedback Loss

GoTo Frequency (b5-13) until the b5-16 time has expired.

Default: 0.0 s

Min.: 0.0

Max.: 120.0

b5-17

(01B5) PID Accel/Decel Time PID Acc/Dec Time

Sets the acceleration and deceleration time to PID setpoint.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

b5-32

(01EE)

<2>

Integrator Ramp Limit

IntegratrRampLim

When set to a value greater than zero, the PI Integrator is forced

to be within +/- this amount of the soft starter output.

Default: 0.0 Hz

Min.: 0.0

Max.: 10.0

B.2 b: Application