HOA Keypad Display

Fault Name

MSL

Net Master Lost

Net Master Lost
The MEMOBUS master has been lost

Cause

Possible Solution

Network Recovery is set to Fault MSL

P9-27 = 3) and no message has been

received from the master within the time set

in P9-26.

• Increase the P9-26 setting to account for network latency.
• Verify that there is a drive on the network with parameter P1-01 set to 3 and P9-27 to 0.
• Check network connections and verify H5-01 and P9-25 settings for all drives on the network.

HOA Keypad Display

Fault Name

NMS

Not Maintaining Setpoint
The setpoint cannot be maintained and P1-17 is set to 0.

Cause

Possible Solution

When the feedback deviates from the

setpoint at a level greater than P1-15, for a

time set in P1-16. This is effective only

when P1-17 is set to 0 (fault).

• Check for a blocked impeller, over cycling, or broken pipe.
• Set the Not Maintaining Setpoint fault characteristics in P1-16 and P1-17.
• Drive response to this condition is controlled by P1-17, Not Maintaining Setpoint Selection.
• Auto-restart of this fault is controlled by L5-50, Setpoint Not Met Retry.

HOA Keypad Display

Fault Name

nSE

Node Setup Error
A terminal assigned to the node setup function closed during run.

Cause

Possible Solution

The node setup terminal closed during run.

Stop the drive when using the node setup function.

A Run command was issued while the node

setup function was active.

HOA Keypad Display

Fault Name

oC

Overcurrent
Drive sensors detected an output current greater than the specified overcurrent level.

Cause

Possible Solution

The motor has been damaged due to

overheating or the motor insulation is

damaged

• Check the insulation resistance.
• Replace the motor.

One of the motor cables has shorted out or

there is a grounding problem

• Check the motor cables.
• Remove the short circuit and reapply power to the drive.
• Check the resistance between the motor cables and the ground terminal .
• Replace damaged cables.

The load is too heavy

• Measure the current flowing into the motor.
• Replace the drive with a larger capacity drive if the current value exceeds the rated current.
• Determine if there is sudden fluctuation in the current level.
• Reduce the load to avoid sudden changes in the current level or switch to a larger drive.

The acceleration or deceleration times are

too short

Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration

time. If it is not possible to set the proper amount of torque, make the following changes:
• Increase the acceleration time (C1-01, C1-03).
• Increase the S-curve characteristics (C2-01 through C2-04).
• Increase the capacity of the drive.

The drive is attempting to operate a

specialized motor or a motor larger than the

maximum size allowed

• Check the motor capacity.
• Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the motor

nameplate.

Magnetic contactor (MC) on the output side

of the drive has turned on or off

Set up the operation sequence so the MC does not trip while the drive is outputting current.

V/f setting is not operating as expected

• Check the ratios between the voltage and frequency.
• Set parameters E1-04 through E1-10 appropriately.
• Lower the voltage if it is too high relative to the frequency.

Excessive torque compensation

• Check the amount of torque compensation.
• Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.

5.2 Fault Detection