Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 242

Advertising
background image

HOA Keypad Display

Fault Name

CE

MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.

Cause

Possible Solution

Faulty communications wiring or an

existing short circuit

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Communication data error occurred due to

noise

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the drive

input power side.

• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if

required.

• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power

supply input.

HOA Keypad Display

Fault Name

CPF11 to CPF14

CPF16 to CPF19

Control Circuit Error

Cause

Possible Solution

There is a self-diagnostic error in the

control circuit

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Connector on the operator is damaged

Replace the operator.

HOA Keypad Display

Fault Name

CPF02

A/D Conversion Error
An A/D conversion error or control circuit error occurred.

Cause

Possible Solution

Control circuit is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF03

Control Board Connection Error
Connection error between the control board and the drive

Cause

Possible Solution

There is a connection error

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Drive fails to operate properly due to noise

interference

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the drive

input power side.

• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if

required.

• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power

supply input.

HOA Keypad Display

Fault Name

CPF06

EEPROM Memory Data Error
Error in the data saved to EEPROM

Cause

Possible Solution

There is an error in EEPROM control

circuit

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

The power supply was switched off while

parameters were being saved to the drive

Reinitialize the drive (A1-03 = 2220, 3330).

5.2 Fault Detection

242

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising