HOA Keypad Display

Minor Fault Name

Geo Params

Chk Q2-05 to Q2-08

Geothermal Mode Parameters
The drive is running at the level set in Q2-03 due to an incorrect setting.

Cause

Possible Solutions

The temperature parameter values are set

incorrectly.

Set the temperature parameters in the following order:

Q2-08 > Q2-07 > Q2-06 > Q2-05

HOA Keypad Display

Minor Fault Name

HCA

Current Alarm
Drive current exceeded overcurrent warning level (150% of the rated current).

Cause

Possible Solutions

Load is too heavy.

Reduce the load for applications with repetitive operations (i.e., stops and starts), or replace the drive.

Acceleration and deceleration times are too

short.

• Calculate the torque required during acceleration and for the inertia moment.
• If the torque level is not right for the load, take the following steps:
• Increase the acceleration and deceleration times (C1-01 through C1-04).
• Increase the capacity of the drive.

A special-purpose motor is being used, or

the drive is attempting to run a motor

greater than the maximum allowable

capacity.

• Check the motor capacity.
• Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range.

The current level increased due to Speed

Search after a momentary power loss or

while attempting to perform a fault restart.

The alarm will only appear briefly. There is no need to take action to prevent the alarm from occurring in

such instances.

HOA Keypad Display

Minor Fault Name

HIFLO

High Flow

High Flow Error
The meter has detected a high flow condition.

Cause

Possible Solution

The flow is too high

Reduce the flow

The measured water flow has risen above

the P6-17 level for the time set in P6-18.

This is only effective when P6-19, High

Flow Select is set to 1 (alarm).

• Set the High Flow fault characteristics in P6-17 and P6-18.
• Drive response to this condition is controlled by P6-19, High Flow Select.
• Auto-restart of this fault is controlled by P6-19, High Flow Select.

HOA Keypad Display

Minor Fault Name

High Feedback High FB Sensed

High Feedback Level Alarm
The feedback signal is too high.

Cause

Possible Solutions

The feedback level has risen above the level

set in P1-11, High Feedback Level

This is only effective when P1-13, High

Feedback Selection, is set to 1 (Alarm and

digital out).

• Decrease the feedback signal.
• Set the High Feedback alarm characteristics in P1-11 and P-12.
• Drive response to this condition is controlled by P1-13, High Feedback Selection.

HOA Keypad Display

Minor Fault Name

HISUC

High Suction

High Section Pressure

Cause

Possible Solution

The suction pressure has fallen below the

level set in Q5-12 for longer than the time

set in Q5-13. This is only effective when

Q5-14, High Suction Pressure Behavior

Select is set to 1 (alarm).

• Reduce the system pressure.
• Set the High Suction Pressure fault characteristics in Q5-12, Q5-13, and Q5-18.
• Drive response to this condition is controlled by Q5-14, High Suction Pressure Behavior Select.
• Auto-restart of this fault is controlled by Q5-14, High Suction Pressure Behavior Select and Q5-15, Suction

Pressure Auto-restart Time.

5.3 Alarm Detection

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

265