H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

15

Frequency detection 3

Freq Detect 3

Closed: When the drive output frequency is less than or equal to the value in L4-03

±L4-04.

16

Frequency detection 4

Freq Detect 4

Closed: When the output frequency is greater than or equal to the value in L4-03

±L4-04.

17

Torque detection 1

(N.C.)

Trq Det 1 N.C.

Open: Overtorque or undertorque has been detected.

18

Torque detection 2

(N.O.)

Trq Det 2 N.O.

Closed: Overtorque or undertorque has been detected.

19

Torque detection 2

(N.C.)

Trq Det 2 N.C.

Open: Overtorque or undertorque has been detected.

1A

During reverse

Reverse Dir

Closed: Drive is running in the reverse direction.

1B

During baseblock

(N.C.)

BaseBlk 2

Open: Drive has entered the baseblock state (no output voltage).

1E

Restart enabled

Dur Flt Restart

Closed: An automatic restart is performed

1F

Motor overload alarm

(oL1)

Overload (OL1)

Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers

this alarm.

20

Drive overheat pre-

alarm (oH)

OH Prealarm

Closed: Heatsink temperature exceeds the parameter L8-02 value.

22

Mechanical weakening

detection

MechFatigue(OL5)

Closed: Mechanical weakening detected.

2F

Maintenance period

Maintenance

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay

may require maintenance.

30

During torque limit

Torque Limit

OLV

OLV

OLV

OLV

Closed: The torque limit has been reached.

37

During frequency

output

During RUN 2

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial

Excitation is being performed.

Closed: Drive is running the motor (not in a baseblock state and DC Injection is

not being performed).

38

Drive enabled

Drive Enable

Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)

39

Watt hour pulse output Watt-hour Pulse

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate

the kWh count.

3C

LOCAL/REMOTE

status

Local

Open: REMOTE

Closed: LOCAL

3D

During speed search

During SpdSrch

Closed: Speed Search is being executed.

3E

PID feedback low

PID Feedback Low

Closed: PID feedback level is too low.

3F

PID feedback high

PID FeedbackHigh

Closed: The PID feedback level is too high.

4A

During KEB Ride-Thru During KEB

Closed: KEB Ride-Thru is being performed.

4C

During fast stop

During Fast Stop

Closed: A Fast Stop command has been entered from the operator or input

terminals.

4D

oH Pre-alarm time limit OH Pre-Alarm

Closed: oH pre-alarm time limit has passed.

4E

Braking transistor fault

(rr)

Brk Trans Fault

Closed: The built-in dynamic braking transistor failed.

Note:

This setting is not available in models 2A0169 to 2A0415 and

4A0088 to 4A1200.

4F

Braking resistor

overheat (oH)

BrkResistOvHeat

Closed: The dynamic braking resistor has overheated.

Note:

This setting is not available in models 2A0169 to 2A0415 and

4A0088 to 4A1200.

50

Waiting to Run

Waiting for Run

Closed: b1-11 Back Spin Timer is active.

51

Sequence timer 1

SeqTimer Disable

Closed: Sequence timer 1 is active.

52

Sequence timer 2

SeqTimer Cancel

Closed: Sequence timer 2 is active.

53

Sequence timer 3

Sequence timer 3

Closed: Sequence timer 3 is active.

54

Sequence timer 4

Sequence Timer 4

Closed: Sequence timer 4 is active.

58

Underload detection

UL6

Closed: Underload is detected.

60

Internal cooling fan

alarm

Fan Alrm Det

Closed: Internal cooling fan alarm

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

353