Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 88
SECTION B-B
(2) GROUND
TERMINALS
CONTROL CIRCUIT
TERMINALS
MAIN CIRCUIT
TERMINALS
Unit: in. [mm]
Figure 2.44 Models 4T0088 and 4T0103
Table 2.23 12-Pulse Models 4T0088 and 4T0103 Terminal and Wire Specifications for Main Circuit and Ground
Drive Model
Terminal
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4T0088
<1>
4T0103
<1>
R/L1, S/L2, T/L3
6 to 250 (13.3 to 127)
M8
9 to 11 (79.7 to 97.4)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
B1, B2
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0 (22.1 to 26.6)
Refer to applicable codes for wire size
M8
9 to 11 (79.7 to 97.4)
<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.
2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss
88
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide