Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 88

Advertising
background image

SECTION B-B

(2) GROUND
TERMINALS

CONTROL CIRCUIT
TERMINALS

MAIN CIRCUIT
TERMINALS

Unit: in. [mm]

Figure 2.44 Models 4T0088 and 4T0103

Table 2.23 12-Pulse Models 4T0088 and 4T0103 Terminal and Wire Specifications for Main Circuit and Ground

Drive Model

Terminal

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4T0088

<1>

4T0103

<1>

R/L1, S/L2, T/L3

6 to 250 (13.3 to 127)

M8

9 to 11 (79.7 to 97.4)

R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
B1, B2

22 to 1/0 (0.3 to 53.5)

M6

2.5 to 3.0 (22.1 to 26.6)

Refer to applicable codes for wire size

M8

9 to 11 (79.7 to 97.4)

<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.

2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss

88

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising