iQpump Quick Setup Parameter Overview (Simplex)

Step

7

Parameter

Value

Description

Reference

Comments

E2-01

Drive Size

Dependent

Motor Rated Cur-
rent

Set to the motor nameplate full load amps.

For submersible motors use service
factor amps (SFA).

E2-04

2

Number of Motor
Poles

Number of motor poles is used to show the correct

motor RPM on the display

Enter ’4’ for an 1800 RPM motor and ‘2’ for a 3600

RPM motor.

Confirm number of poles

2 Pole Motor = 3600 RPM

4 Pole Motor = 1800 RPM

6 Pole Motor = 1200 RPM

8 Pole Motor = 900 RPM

P1-03

145

Feedback Device
Scaling

System Scaling: Enter feedback device maximum:

Example: Enter 200 for pressure transducer with a

maximum of 200 PSI at 20mA.

Confirm feedback device scaling.

(See Illustration 1)

Q1-01

0

Setpoint 1

Set System Setpoint

Set to system pressure

P1-04

0.0 PSI

Start / Drawn
Down Level

When the iQpump is turned On and the feedback

signal level (transducer) falls below this level, the

pump system will start after the time specified in P1-

05 (default 1 sec).

Programming the Start Level as an Absolute

Value. Start / Draw Down Level has to programmed

to a positive value in order for the Start / Draw Down

Level to be an absolute value. Example: Start /

Draw Down Level P1-04 set to 50 PSI and delay

time P1-05 set to 5 sec. Pump system will start

when the pressure drops below 50 PSI for 5 sec.

Programming the Start Level as a Delta Level

from the System Setpoint

Start / Draw Down Level has to programmed to a

negative value in order for the Start Level to be a

delta value from the setpoint.

Example: Start / Draw Down Level P1-04 set to –10

PSI with a system setpoint of 50 PSI and a delay

time P1-05 set to 5 sec. Pump system will start

when the pressure drops below 40 PSI (50 - 10) for

5 sec.

It is mandatory to program the Start / Draw

Down Level in order to use the sleep func-

tion.

(See Illustration 2 and 3)

P1-06

40.0 Hz

Minimum Pump
Speed

Minimum speed (Hz) the pump motor has to operate

at. Example: Base pump motor speed is 3600 RPM,

minimum speed is 2400 RPM. Set

minimum pump frequency to 40.0 Hz. (2400 ÷ 3600

x 60 Hz = 40 Hz)

Minimum pump frequency should be set to

a value where the pump enters a no-flow

condition.

P4-10

0

Disabled

Auto Mode Opera-
tor Run Power
Down
Storage

Stores the run status in the Auto mode when operat-
ing from digital operator (b1-02=0).
0: Disabled
1: Enabled

Recommended for use when Start/Stop

command is from the keypad.

(See Step 9)

P5-04

1

Enabled

Hand Key
Enable / Disable

Enables or disables the Hand Key on the digital op-
erator.
0: Disabled
1: Enabled

Hand Key on keypad.

(See Step 10)

A1-06

Dependent on

Initialization

Mode

Application
Selected

Displays selected applications, see Step 6.

Read-only cannot be modified

Use

to change the sign.

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide