Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 348

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H1-28

(02DE) External Fault 8 Delay

Time

EF8 Delay Time

Sets the amount of time delay applied to the EF8 fault.

(20 ≤ H1-08 ≤ 2F)

Default: 0.00 s

Min.: 0.00

Max.: 300.00

<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

0

3-Wire sequence

3-Wire Control

Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)

Terminals S1 and S2 are automatically set up for the Run command and Stop

command.

2

External Reference 1/2

Selection

External Ref 1/2 Sel

Open: Run command and frequency reference source 1 (determined by b1-01 and

b1-02)

Closed: Run command and frequency reference source 2 (determined by b1-15

and b1-16)

3

Multi-Step Speed

Reference 1

Multi-Step Ref 1

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

4

Multi-Step Speed

Reference 2

Multi-Step Ref 2

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

5

Multi-Step Speed

Reference 3

Multi-Step Ref 3

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

6

Jog reference selection jog Freq Ref

Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other

reference sources.

7

Accel/decel time

selection 1

Multi-Acc/Dec 1

Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel

time 2

(set in C1-03, C1-04).

8

Baseblock command

(N.O.)

Ext BaseBlk N.O.

Closed: No drive output

9

Baseblock command

(N.C.)

Ext BaseBlk N.C.

Open: No drive output

A

Accel/decel ramp hold

Acc/Dec RampHold

Open: Accel/decel is not held

Closed: The drive pauses during acceleration or deceleration and maintains the

output frequency.

B

Drive overheat alarm

(oH2)

OH2 Alarm Signal

Closed: Closes when an oH2 alarm occurs

C

Analog terminal input

selection

Term A2 Enable

Open: Function assigned by H3-14 is disabled.

Closed: Function assigned by H3-14 is enabled.

F

Through mode

Term Not Used

Select this setting when using the terminal in a pass-through mode. The terminal

does not trigger a drive function but can be used as digital input for the controller

the drive is connected to.

10

Up command

Up Command 1

The drive accelerates when the Up command terminal closes, and decelerates when

the Down command closes. When both terminals are closed or both are open, the

drive holds the frequency reference. The Up and Down commands must always

be used in conjunction with one another.

11

Down command

Down Command 1

The drive accelerates when the Up command terminal closes, and decelerates when

the Down command closes. When both terminals are closed or both are open, the

drive holds the frequency reference. The Up and Down commands must always

be used in conjunction with one another.

12

Forward Jog

Forward Jog

Closed: Runs forward at the Jog frequency d1-17.

13

Reverse Jog

Reverse Jog

Closed: Runs reverse at the Jog frequency d1-17.

14

Fault reset

Fault Reset

Closed: Resets faults if the cause is cleared and the Run command is removed.

15

Fast Stop (N.O.)

Fast-Stop N.O.

Closed: Decelerates at the Fast Stop time set to C1-09.

17

Fast Stop (N.C.)

Fast-Stop N.C.

Open: Decelerates to stop at the Fast Stop time set to C1-09.

18

Timer function input

Timer function

Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction

with the timer function output (H2-oo = 12).

19

PID disable

PID Disable

Open: PID control enabled

Closed: PID control disabled

B.7 H Parameters: Multi-Function Terminals

348

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide