C.4 MEMOBUS/Modbus Setup Parameters

u

MEMOBUS/Modbus Serial Communication

Changes to MEMOBUS/Modbus communications settings become effective after restarting the drive.

n

H5-01: Drive Node Address

Sets the drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S- . .

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-01

Drive Slave Address

0 to FF

1F (Hex)

Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value

besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but no

two drives may share the same address.

n

H5-02: Communication Speed Selection

Sets the MEMOBUS/Modbus communications speed.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-02

Communication Speed Selection

0 to 8

3

H5-02

Communication Speed

H5-02

Communication Speed

0

1200 bps

5

38400 bps

1

2400 bps

6

57600 bps

2

4800 bps

7

76800 bps

3

9600 bps

8

115200 bps

4

19200 bps

n

H5-03: Communication Parity Selection

Sets the parity used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-03

Communication Parity Selection

0 to 2

0

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n

H5-04: Stopping Method after Communication Error

Selects the stopping method after a communications error (CE) has occurred.

No.

Name

Setting Range

Default

H5-04

Stopping Method after CE

0 to 3

3

Setting 0: Ramp to stop (uses the deceleration time currently enabled)
Setting 1: Cost to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)

n

H5-05: Communication Fault Detection Selection

Enables or disables the CE detection for communications.

No.

Name

Setting Range

Default

H5-05

Communication Fault Detection Selection

0 or 1

1

C.4 MEMOBUS/Modbus Setup Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

417

C

MEMOBUS/Modbus Communications