Flange Type Heat Loss Data

Table 2.14 Models 2A0030 and 2A0040, 4A0018 and 4A0023, and 5A0011

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

2A0030

200

117.1

261.5

378.6

92.3

194.4

286.7

4.2 (9.2)

2A0040

144.5

292.8

437.3

104.8

213.8

318.6

4.2 (9.2)

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

4A0018

400

108.0

177.3

285.3

85.7

135.4

221.1

4.1 (9.0)

4A0023

138.1

215.9

354.0

97.0

149.9

246.9

4.1 (9.0)

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

5A0011

600

88.0

56.1

144.1

49.5

110.9

160.4

4.1 (9.0)

2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss