S3: secondary pi (pi2) control – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 397

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S2-15

(3214)

Sequence Timer 3

Reference Source

Tmr 3 Ref Source

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial com

6: Option PCB

7: Pulse Input

8: Set by b1-01

Selects the frequency reference source used for running the

drive when sequence timer 3 is active (only applicable when

S2-14 is set to 1 or 2).

0: Operator (d1-01/Q1-01)

1: Operator (d1-02/Q1-02)

2: Operator (d1-03/Q1-03)

3: Operator (d1-04/Q1-04)

4: Terminals

5: Serial communication

6: Option card

7: Pulse input

8: Set by b1-01

Default: 8

Range: 0 to 8

S2-16

(3215)

Sequence Timer 4 Start

Time

Tmr 4 Start Time

Sets the start time for timer 4. The value must be set less than

or equal to S2-17.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-17

(3216)

Sequence Timer 4 Stop

Time

Tmr 4 Stop Time

Sets the stop time for timer 4. The value must be set greater than

or equal to S2-16.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-18

(3217)

Sequence Timer 4 Day

Selection

Tmr 4 Day Sel

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Sets the days for which sequence timer 4 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

S2-19

(3218)

Sequence Timer 4

Selection

Tmr 4 Seq Sel

0: Digital out only

1: Run

2: Run - PI Disable

Sets the action that occurs when sequence timer 4 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

S2-20

(3219)

Sequence Timer 4

Reference Source

Tmr 4 Ref Source

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial com

6: Option PCB

7: Pulse Input

8: Set by b1-01

Selects the frequency reference source used for running the

drive when sequence timer 4 is active (only applicable when

S2-19 is set to 1 or 2).

0: Operator (d1-01/Q1-01)

1: Operator (d1-02/Q1-02)

2: Operator (d1-03/Q1-03)

3: Operator (d1-04/Q1-04)

4: Terminals

5: Serial communication

6: Option card

7: Pulse input

8: Set by b1-01

Default: 8

Range: 0 to 8

<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.

u

S3: Secondary PI (PI2) Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S3-01

(321A) Secondary PI Enable

Selection

PI2 Enable Sel

0: Disabled

1: Always

2: Drive running

3: Motor running

Determines when the secondary PI controller is enabled.

0: Disabled

1: Always

2: Drive running

3: Motor running

Note:

Setting 3 does not run the motor at zero speed,

baseblock, or in DC injection.

Default: 0

Range: 0 to 3

S3-02

(321B) Secondary PI User

Display

PI2 UsrDspMaxVal

Sets the scale value of 100% PI input.

Default: 10000

Min.: 0

Max.: 60000

B.13 S: Special Application

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

397

B

Parameter List