Setting the Drive Networking Parameters

1.

1. Set parameter H5-01, Serial Node Address, on each drive.

Note:

For optimal performance, use consecutive numbers starting from 1. Parameter setting H5-01 must be unique for each drive.

2.

Set parameter P9-25, Highest Node Address, on each drive.

Note:

For optimal performance, set to highest H5-01 value. This setting must be the same for all the drives on the network.

3.

Set P1-01 to 3 (MEMOBUS/Modbus Network) on all the drives.

4.

Cycle main power to all networked drives.

Note:

The H5-01 setting will not take effect until power is cycled to the drive and may cause communication errors and unexpected

behavior.

Verifying the iQpump1000 Drive Network Communications

Access monitor U9-02, Network Activity, and verify:
• No drives have a value of 0 <->
• All drives are receiving valid data indicated by a regular change in the monitor value.
• At least one drive has the unit <M>, while the others have the unit <+>.

Table 4.8 Network Connectivity Information

Network State

Top Line on Home Screen

(o1-12 = 1)

U9-02 Network Activity

Drive is the Master and is

communicating with another

drive.

Pump Off Network

<M> CONNECTED

<- MONITOR - >

U5-99=

U1-02=

U1-91=

100.0

PSI

0.00Hz

62.8PSI

Network Activity

U9-02=

U1-02=

U1-91=

9453

<M>

0.00Hz

62.8PSI

- MONITR -

DRV RDY

Home

FWD

Drive is a node on the network and

is communicating with a Master.

Pump Off Network

<+> CONNECTED

<- MONITOR - >

U5-99=

U1-02=

U1-91=

100.0

PSI

0.00Hz

62.8PSI

Network Activity

U9-02=

U1-02=

U1-91=

324

<+>

0.00Hz

62.8PSI

- MONITR -

DRV RDY

Home

FWD

Drive is not able to communicate

to any other drives.

Pump Off Network

<-> DISCONNECTED

<- MONITOR - >

U5-99=

U1-02=

U1-91=

100.0

PSI

0.00Hz

62.8PSI

Network Activity

U9-02=

U1-02=

U1-91=

0

<->

0.00Hz

62.8PSI

- MONITR -

DRV RDY

Home

FWD

If a drive displays U9-02 = 0 <->:
• Check physical connections.
• Verify the H5-oo serial communication settings.
• Confirm the P9-25 and P9-27 settings on all the drives. P9-25 should be set to the highest H5-01 address and at least one

drive should have P9-27 set to 0.

• Cycle main power.

Multiplexing Principle

Always observed by system:
• New drives start as Lead and run in PI mode.
• Only the Lead drive can request staging and de-staging.
• Staging will start a new Lead drive and make the old Lead drive into a Lag drive.

4.5 iQpump Presets and Functions

198

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide