B.13 S: Special Application

u

S1: Dynamic Noise Control Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S1-01

(3200)

Dynamic Audible Noise

Control Function

Selection

Dyn Noise Ctrl

0: Disabled

1: Enabled

V/f

V/f

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

S1-02

(3201)

Voltage Reduction Rate Volt Reduce Amt

V/f

V/f

Sets the rate at which the output voltage will be reduced as a

percentage of the V/f pattern when operating with no load.

Default: 50.0%

Min.: 50.0

Max.: 100.0

S1-03

(3202)

Voltage Restoration

Level

V Reduce On Lvl

V/f

V/f

Sets the level when the drive should start restoring the voltage

as a percentage of the drive rated torque.

Default: 20.0%

Min.: 0.0

Max.: 90.0

S1-04

(3203)

Voltage Restoration

Complete Level

V Reduce Off Lvl

V/f

V/f

Sets the level at which voltage restoration for the V/f pattern is

complete as a percentage of the drive rated torque. If the output

torque rises above the value of S1-04, then the voltage will be

controlled in a manner specified by the V/f pattern setting.

Default: 50.0%

Min.: S1-03 +

10.0

Max.: 100.0

S1-05

(3204)

Voltage Restoration

Sensitivity Time

Constant

Sensitivity Time

V/f

V/f

Sets the level of sensitivity of the output torque and LPF time

constants for the voltage reduction rate. The level of sensitivity

can be adjusted in accordance with the load response.

Default: 1.000 s

Min.: 0.000

Max.: 3.000

S1-06

(3205)

Voltage Restoration

Time Constant at Impact Impact Load Time

V/f

V/f

Sets the voltage restoration time constant if an impact load is

added.

Default: 0.050 s

Min.: 0.000

Max.: 1.000

u

S2: Programmable Run Timers

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S2-01

(3206)

Sequence Timer 1 Start

Time

Tmr 1 Start Time

Sets the start time for timer 1. The value must be set less than

or equal to S2-02.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-02

(3207)

Sequence Timer 1 Stop

Time

Tmr 1 Stop Time

Sets the stop time for timer 1. The value must be set greater than

or equal to S2-01.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-03

(3208)

Sequence Timer 1 Day

Selection

Tmr 1 Day Sel

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Sets the days for which sequence timer 1 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

S2-04

(3209)

Sequence Timer 1

Selection

Tmr 1 Seq Sel

0: Digital out only

1: Run

2: Run - PI Disable

Sets the action that occurs when sequence timers 1 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

B.13 S: Special Application

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

395