5 iqpump presets and functions – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 187

Advertising
background image

No.

Name

Description

Values

P9-30

Lag Drive Speed Follower Gain

Sets the gain to be applied to the speed of the current lead drive when P9-05 is set

to 3. The bias to be applied is set in P9-31.

Default: 100.0%

Min.: 0.0

Max.: 300.0

P9-31

Lag Drive Speed Follower Bias

Sets the bias to be applied to the speed of the current lead drive when P9-05 is set

to 3. The gain to be applied is set in P9-30.

Default: 0.00 Hz

Min.: -60.0

Max.: 60.0

P9-32

Lag Follower Deceleration

Time

Sets the deceleration time when the P9-33 timer is running and the drive is running

as Lag Drive Speed Follower (P9-05 is set to 3).

Default: 60.0 s

Min.: 0.0

Max.: 1000.0

P9-33

Lag Follower Deceleration

Time Active Time

Sets the time during which the deceleration time set in P9-32 is effective. The drive

will use the standard deceleration rate when it expires.

Setting this parameter to 0.0 disables the function.

Default: 0.0 s

Min.: 0.0

Max.: 360.0

P9-99

Network Compatibility

Selection

Determines the communication compatibility for the iQPump MEMOBUS

network.

0: A-Ver: 30034

1: B-Ver: 30035/36

2: iQ Smart Network

Default: 2

Range: 0 to 2

Timing Diagrams - Speed Follower Deceleration Time Switchover (Disabled and Enabled)

P9-07

Lag

Fixed

Delay

P9-07

Lag

Fixed

Delay

Drive 1

Drive 1

Drive 2

Drive 2

Drive 3

Drive 3

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

Drive 3 Staged-in.

Drive 2 becomes a Lag

Drive and latches to its

current output speed.

Drive 3 is no longer needed and gets de-

staged.

Drive 2 is the Lead again.

Drive 1 follows the speed of Drive 2 again.

Output Frequency

Output Frequency

Output Frequency

Output Frequency

Output Frequency

Output Frequency

Add Freq Level P9-09

Add Freq Level P9-09

Add Freq Level P9-09

Add Freq Level P9-09

Add Freq Level P9-09

Add Freq Level P9-09

Remove Freq Level P9-13

Remove Freq Level P9-13

Remove Freq Level P9-13

Remove Freq Level P9-13

Remove Freq Level P9-13

Remove Freq Level P9-13

Start-up…

Drive 1 is the

Lead Pump.

Drive 2 Staged-in.

Drive 1 becomes a Lag

Drive and latches to its

current output speed.

Drive 1 follows the

speed of Drive 2

(Lead)

Drive 1 and Drive 2

follows the speed of

Drive 3 (Lead)

P9-01 = 1 (Lowest Run-time)
P9-08 = 0 (Output Frequency)
P9-32 = 60.0 sec

P9-05 = 3 (Follow Lead Speed)
P9-12 = 0 (Output Frequency)
P9-33 = 0.0 sec

Figure 4.14 Lag Follower Deceleration Time Switching (Disabled)

4.5 iQpump Presets and Functions

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

187

4

Start-Up Programming & Operation