C.12 Self-Diagnostics

The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosis

function, use the following procedure.

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or

serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply

is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least

one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

1.

Turn on the power to the drive.

2.

Note the present terminal S6 function selection setting (H1-06) and set it for the communications test mode

(H1-06 = 67).

3.

Turn off the power to the drive.

4.

With the power off, wire the drive as shown in

Figure C.8

, connecting terminals R+ and S+, R- and S-, and S6 and

SC.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

Figure C.8 Terminal Connections for Communication Self-Diagnostics

5.

Set jumper S3 to source mode (internal power supply).

6.

Turn the power to the drive back on.

7.

During normal operation, the drive will display “Pass” to indicate that the communications test mode is operating

normally.
When a fault occurs, the drive will display “CE” on the keypad display.

8.

Turn off the power supply.

9.

Remove the wire jumpers from terminal R+, R-, S+, S-, and S6-SC. Reset jumper S3 to its original position and set

terminal S6 to its original function.

10.

Return to normal operation.

C.12 Self-Diagnostics