u

b6: Dwell Function

No.

(Addr.

Hex)

Name

Description

Values

Page

b6-01

(01B6) Dwell Reference at Start Dwell Ref @Start

Parameters b6-01 and b6-02 set the frequency to hold and the

time to maintain that frequency at start.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b6-02

(01B7) Dwell Time at Start

Dwell Time @Start

Default: 0.0 s

Min.: 0.0

Max.: 10.0

b6-03

(01B8) Dwell Reference at Stop Dwell Ref @Stop

Parameters b6-03 and b6-04 set the frequency to hold and the

time to maintain that frequency at stop.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b6-04

(01B9) Dwell Time at Stop

Dwell Time @Stop

Default: 0.0 s

Min.: 0.0

Max.: 10.0

u

b8: Energy Saving

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b8-01

(01CC)

Energy Saving Control

Selection

Energy Save Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

b8-02

(01CD) Energy Saving Gain

Energy Save Gain

OLV

OLV

OLV

OLV

Sets the gain used for Energy Saving.

Default: 0.7

Min.: 0.0

Max.: 10.0

b8-03

(01CE) Energy Saving Control

Filter Time Constant

Energy Save F.T

OLV

OLV

OLV

OLV

Sets a time constant for Energy Saving.

Default:

<1>

Min.: 0.00 s

Max.: 10.00 s

b8-04

(01CF)

Energy Saving

Coefficient Value

Energy Save COEF

V/f

V/f

Determines the level of maximum motor efficiency. Setting

range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display

resolution depends on the rated output power of the drive.

Default:

<1> <2>

Min.: 0.00

Max.: 655.00

b8-05

(01D0)

Power Detection Filter

Time

kW Filter Time

V/f

V/f

Sets a time constant filter for output power detection.

Default: 20 ms

Min.: 0

Max.: 2000

b8-06

(01D1)

Search Operation

Voltage Limit

Search V Limit

V/f

V/f

Sets the limit for the voltage search operation as a percentage of

the motor rated voltage.

Default: 0%

Min.: 0

Max.: 100

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.