B3-01: speed search selection at start, B5-01: pid function setting – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 214

Advertising
background image

Setting 3: Coast to Stop with Timer (Used for Back Spin Control on Vertical Turbine Pumps)

When the Run command is removed, the drive coasts to a stop. If parameter b1-11 is set to zero, the coast-timer (Run Delay

at Stop) becomes a value determined by a combination of output frequency and the C1-02 parameter. However, if b1-11 is set

greater than zero, the Run Delay at Stop timer is set to b1-11. If the Run command is re-issued during the Run Delay at Stop

timer time, the drive WILL restart when the timer expires without the need to re-cycle the Run command. The Run Delay at

Stop timer will operate for both AUTO Mode and HAND Mode. The Run Delay at Stop timer will still operate when the drive

goes to sleep and then wakes up. During the Run Delay at Stop timer execution, the HOA keypad will display the alarm

“WrUn”. Both Alarm and Run indicators will blink while the drive waits to execute the Run command.

Drive output shut off

Run wait time t

Run command

Output

frequency

ON

ON

ON

OFF

OFF

Figure 4.34 Coast to Stop with Timer

The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.

Min output

frequency

100%

(Max output

frequency)

Output frequency

when Stop command

was entered

Run wait time t

Active deceleration time

Min Baseblock Time (L2-03)

Figure 4.35 Run Wait Time Depending on Output Frequency

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

0

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search

is complete.

n

b5-01: PID Function Setting

Enables and disables the PID operation and selects the PID operation mode.

No.

Parameter Name

Setting Range

Default

b5-01

PID Function Setting

0, 1

0

Setting 0: PID disabled

Setting 1: Output frequency = PID output 1

The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.

4.6 Basic iQpump Setup and Application Preset Parameters

214

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide