Setting 7770: General Purpose

General Purpose Application Preset.

Refer to Pump Application Presets on page 169

for a list of parameters and default values

for this Application Preset.

Setting 7771: Submersible Motor General Purpose Operation

General Purpose Application Preset.

Refer to Pump Application Presets on page 169

for a list of parameters and default values

for this Application Preset.

n

b1-01: Frequency Reference Selection 1

Selects the frequency reference source 1 for the REMOTE mode.

Note:

If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED

on the digital operator will light and the STOP indicator will flash.

No.

Parameter Name

Setting Range

Default

b1-01

Frequency Reference Selection 1

0 to 5

0

In order to run the drive and motor, the drive must receive a Run command and an Auto Setpoint command. Parameter b1-01

specifies the origin of the Auto setpoint when in AUTO Mode. Switch to AUTO mode by pressing the AUTO button on the

HOA keypad while the drive is stopped.

Note:

If a Run command is input to the drive without a corresponding Auto setpoint, the Run indicator on the HOA keypad will turn on and the

STOP indicator on the keypad will blink.

If the drive should follow the “HAND Reference” set by the HOA keypad, use HAND Mode by pressing the HAND key and

set P5-01 to “1: Hand Reference (P5-02).” The HAND reference can then be entered into the U1-01 monitor parameter in the

“-DRIVE- ” Menu.
The drive offers the ability to provide four types of “Auto Setpoint” reference sources. These Auto Setpoint reference sources

are determined by the setting of b1-01 and the drive set to AUTO Mode by pressing the AUTO key on the keypad.
Prior to programming, it is recommended to select the system units (P1-02) and the feedback device, Scaling (P1- 03) first.

P1-03 will automatically scale the drive setpoint.
Example: P1-02 = 1: PSI
P1-03 = 200, feedback range = 200 PSI.
If the drive should follow an “Auto Set-Point” set by the HOA keypad: Set b1-01 to “0: Operator” (factory default). The Auto

setpoint can then be entered into the U1-01 monitor parameter in the “-DRIVE-” menu.

Setting 0: Operator (HOA keypad)

Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.
This selection will also switch PID setpoint to Q1-01.

Setting 1: Terminals (analog input terminals)

Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
To set the drive to follow an “Auto Setpoint” set by the analog input, set b1-01 to 1 (Terminals) and connect a potentiometer

or external signal to the drive.

Note:

When b1-01 is set to 1 (Terminals) and P5-01 is set to 0 (HAND Mode Reference), the setpoint and the HAND reference are determined

by the external analog signal.

Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in

Table 4.17

for the input

used.

Table 4.17 Analog Input Settings for Frequency Reference Using Voltage Signals

Terminal

Signal Level

Parameter Settings

Notes

Signal Level

Selection

Function Selection

Gain

Bias

A1

0 to 10 Vdc

H3-01 = 0

H3-02 = 0

(Frequency Reference Bias)

H3-03

H3-04

0 to 10 Vdc

Bipolar

H3-01 = 1

4.6 Basic iQpump Setup and Application Preset Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

209