Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 376

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P2-07

(0C6A) Sleep Boost Maximum

Time

SleepBoost MaxTm

Sets the amount of time that the system (feedback) has to reach

the boosted setpoint. The drive will go to sleep when the amount

of time set in this parameter has been exceeded.

Default: 20.0 s

Min.: 1.0

Max.: 160.0

P2-08

(0C6B) Delta Sleep Feedback

Drop Level

D Fb Drop Level

If the PID Error (setpoint minus feedback) exceeds the level

programmed in this parameter within the time window set in

P2-09 and the output frequency is greater than the level set in

P1-06, the sleep operation deactivates and the drive returns to

normal operation.

Setting this parameter to 0.0 disables the function.

Default: 0.0 PSI

<3>

Min.: 0.0

Max.: 6000.0

P2-09

(0C6C) Feedback Detection

Drop Time

FB Drop Det. Time

Defines the time window in which the software monitors the

feedback to detect a flow/no-flow condition.

Default: 10.0 s

Min.: 0.0

Max.: 3600.0

P2-10

(0C6D) Sleep Mode: Cycling

Protection

Cycle Protection

Sets the maximum number of cycles that are allowed within the

time specified in P2-11 before tripping the PoC “Pump Over

Cycle” fault.

One cycle is defined when the drive transfers from normal

operation in AUTO Mode to Sleep Mode.

This function is active when the drive is running during AUTO

Mode. When P1-01 is set to 3 (MEMOBUS network), the

function is active when there is only one drive running on the

network.

Setting this parameter to 0 disables the function.

Default: 0

Min.: 0

Max.: 10

P2-11

(0C6E)

Sleep Mode: Maximum

Cycling Protection

Time

Max. Cycle Time

Sets the maximum time allowed between cycles. When no

cycling occurs within the programmed time, the drive will

decrease the internal cycle register.

Default: 300 s

Min.: 0

Max.: 3600

P2-12

(0C6F) Over Cycling Mode

Over Cycle Mode

0: Disabled

1: Alarm Only

2: Fault

3: Auto SP Comp.

0: Disabled

1: Alarm

2: Fault

3: Auto SP Compensation

Default: 0

Range: 0 to 3

P2-13

(0C70) Setpoint Compensation Setpoint Comp.

Allows for the software to automatically compensate the

setpoint in the event of excessive cycling.

Default: 0.0 PSI

<3>

Min.: 0.0

Max.: 6000.0

P2-14

(0C71)

Maximum Setpoint

Compensation

Max. SP Comp.

Sets the maximum allowed setpoint compensation for over-

cycling function.

Default: 0.0 PSI

<3>

Min.: 0.0

Max.: 6000.0

P2-23

(0C7A) Anti-No-Flow

Bandwidth

ANF Bandwidth

Sets the amount of PI error bandwidth used to detect the Anti-

No-Flow condition.

Avoid setting this parameter value too high, as operation may

become unstable.

Setting this parameter to 0.00 will disable the function.

Default: 0.40%

Min.: 0.00

Max.: 2.00

P2-24

(0C7B) Anti-No-Flow

Detection Time

ANF Det. Time

Sets the time delay before the drive starts the increased

deceleration rate after Anti-No-Flow is detected.

Default: 10.0 s

Min.: 1.0

Max.: 60.0

P2-25

(0C7C) Anti-No-Flow Release

Level

ANF Release Lvl

Sets the amount below the setpoint which the feedback must

drop to disengage the Anti-No-Flow and return to normal PI

operation.

Default: 3.0 PSI

<3>

Min.: 0.0

Max.: 100.0

<1> Display units vary depending on the setting for P2-01, Sleep Level Type. When P2-01 is set to 0, the display units are “Hz”; setting 1 is “A”; setting

2 is P1-02 Selection; setting 3 is “RPM”; setting 4 is P6-04 selection.

<2> Display units vary depending on the setting for P2-01, Sleep Level Type. When P2-01 is set to 0, 1, 2, or 4, the display units are “Hz”; setting 3 is

“RPM”.

<3> Unit is determined by P1-02, System Units, setting.

B.11 P: Pump Parameters

376

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide