K setting, Hot and cold safe stall time – Basler Electric BE1-11m User Manual

Page 110

Advertising
background image

98

9424200996 Rev L

The Voltage Configuration screen is shown in Figure 68.

Figure 68. User Table Curve, Voltage Configuration Screen

Table 37 summarizes the voltage configuration settings.

Table 37. Settings for Voltage Configuration

Setting

Range

Increment

Unit of Measure

Default

Curve 1 Voltage

20 to 100

1

percent

100

Curve 2 Voltage & Curve 3 Voltage

0 or 20 to 100

1

percent

0

K Setting

The K setting determines how much the negative-sequence current will bias the equivalent thermal
current calculated by the BE1-11m. The equivalent thermal current is calculated in Equation 7. If the IEC
Curve is being used, then I

eq

is fixed at zero and this equation is not necessary.

I

eq

= I�1 + k �

I

2

I

1

2

Equation 7. Equivalent Thermal Current

Where:

I

eq

= equivalent thermal current in pickup (unit of thermal pickup current)

I = maximum phase current in pickup

I

1

= positive-sequence fundamental component of current in pickup

I

2

= negative-sequence fundamental component of current in pickup

k = constant used to determine additional heating from negative-sequence current in pickup

Hot and Cold Safe Stall Time

The Hot and Cold Safe Stall Time settings determine the thermal capacity level that is reached for
currents less than the 49TC pickup. The Running and Stopped Cool Time Constant settings determine
the rate at which the thermal capacity increases or decreases for currents less than the 49TC pickup. The
thermal capacity calculations are shown in Equation 8 and Equation 9. If the IEC Curve is being used,
then I

eq

= 0.

TCU

end

= �

I

eq

S ∙ SF ∙ FLA� ∙ �1 −

hot safe stall time

cold safe stall time�

Equation 8. TCU

end

Thermal Curve (49TC) Protection

BE1-11m

Advertising