Power quality, Power quality settings, Retrieving power quality data – Basler Electric BE1-11m User Manual

Page 193

Advertising
background image

9424200996 Rev L

181

Power Quality

The BE1-11m offers class B power quality measurement performance as defined by IEC 610004-30.
Power quality data consists of voltage, distortion, dips/swells, and harmonics. Power quality is reported
through BESTCOMSPlus

®, the front-panel interface, and the web page interface. Refer to the

BESTnet

™Plus

chapter for information on viewing the demands through the web page interface.

Power Quality Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Metering Configuration, Power Quality

HMI Navigation Path: Settings Explorer, Metering Configuration, Power Quality

Settings are made using BESTCOMSPlus. Use the Settings Explorer to open the Metering Configuration,
Power Quality tree branch. The Power Quality screen is illustrated in Figure 143.

Figure 143. Metering Configuration, Power Quality Screen

Table 71 summarizes the power quality settings.

Table 71. Power Quality Settings

Setting

Range

Increment

Unit of Measure

Default

Reference Mode

Fixed or Sliding

n/a

n/a

Fixed

Dip Hysteresis

1 to 1.3

0.01

units

1

Dip Ratio

0 or 0.7 to 1

0.01

units

0

Swell Hysteresis

0.7 to 1

0.01

units

1

Swell Ratio

0 or 1 to 1.3

0.01

units

0

Retrieving Power Quality Data

BESTCOMSPlus Navigation Path: Metering Explorer, Power Quality

HMI Navigation Path: Metering Explorer, Power Quality

Power quality data can be viewed using BESTCOMSPlus, through the front-panel interface, and through
the web page interface. To view data using BESTCOMSPlus, use the Metering Explorer to open the
Power Quality tree branch.

BE1-11m

Power Quality

Advertising