Retrieving oscillographic records, O table 61, N figure 118 – Basler Electric BE1-11m User Manual

Page 166

Advertising
background image

154

9424200996 Rev L

Figure 118. Fault Records Screen

Table 61 summarizes the oscillographic records settings.

Table 61. Oscillographic Records Settings

Setting

Range

Increment

Default

Sample Resolution

32, 16, or 8

n/a

32

Number of Records to Store

32, 16, 8, or 4

n/a

32

Prefault Cycles

0 to 16

1

2

Retrieving Oscillographic Records

Oscillographic records can be downloaded through the Reports, Fault Reports screen in BESTCOMSPlus
(Figure 117). See Fault Reports earlier in this chapter. Oscillographic records can also be downloaded
through the web page interface. For more information, refer to the

BESTnetPlus

chapter.

Fault Reporting

BE1-11m