Oscillator mode, Integrating timer mode, Block initiate 62-x – Basler Electric BE1-11m User Manual

Page 431

Advertising
background image

9424200996 Rev L

419

Note

The 43-1 switch action is performed three times in this test. To
illustrate the action of the timer mode, step 4 should be executed as
quickly as possible for the second 43-1 switch action (within 15
second duration of the pickup time delay). Perform step 4 again for the
third 43-1 switch action after at least 15 seconds (the pickup timer
setting) have elapsed but before the 20 second dropout time delay
expires. This will illustrate the action of the timer mode. The time delay
settings can be increased if difficulty is encountered with repeating the
43-1 switch actions.

Step 7: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events

screen. Verify that approximately 15 seconds after the second 43-1 OFF to ON initiate signal,
the 62-1 timer output went true. Verify that the timer output went false when the third OFF to ON
initiate signal forced the 62-1 time delay 1 to restart. Figure 280 illustrates the timing
relationship of the 43-1 switch and 62-1 timer.

Figure 280. One-Shot/Retriggerable Mode

Step 8: (Optional.) Repeat steps 1 through 7 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Oscillator Mode

Because this operating mode is not intended for general use, no testing procedure is available.
Information about Oscillator mode is available in the

Logic Timers (62)

chapter.

Integrating Timer Mode

Step 1: Use BESTCOMSPlus to send the operational settings in Table 185 to the BE1-11m. Retain the

logic settings from Figure 276.

Table 185. Operational Settings (Integrating Timer Mode)

Setting

Value

BESTCOMSPlus Screen

Description

62-1 Mode

Integrating
Timer

Control, Logic Timers (62)

Sets 62-1 to Integrating Timer
mode

62-1 Time Delay 1
(T1)

15,000 ms

Control, Logic Timers (62)

Sets 62-1 pickup time delay to
15,000 ms

62-1 Time Delay 2
(T2)

5,000 ms

Control, Logic Timers (62)

Sets 62-1 dropout time delay to
5,000 ms

43-1 Mode

Switch

Control, Virtual Control
Switches (43)

Sets 43-1 to Switch mode

62-1 Target

Enabled

Target Configuration, Targets
screen.

Enables 62-1 target

P

0

0

3

5

-3

2

0

2

-2

7

-0

6

Block

Initiate

62-x

BE1-11m

Logic Timers (62) Test