508

9424200996 Rev L

Figure 332. Login Screen

Enter the Password and then click the Log In button. The default password is “OEM”. The Device Security
Setup screen shown in Figure 333 appears.

Figure 333. Device Security Setup Screen

A password is changed by clicking on the access level and entering the new password. Click the Save
Password button to save the settings to BESTCOMSPlus memory.

Pull down the Communication menu and select Upload Security to Device. The Login dialog box pops up.
An OEM access level is required to upload security settings to the device.

Enter the password and then click the Log In button. The default password is “OEM”. BESTCOMSPlus
notifies you when the upload is successful.

Remote Analog Inputs Configuration

The RTD module provides four analog inputs. The BE1-11m supports two RTD modules at once. To
make identifying the analog inputs easier, a user-assigned name can be given to each input.

Protection settings for remote analog inputs are described in the

Analog Input Protection

chapter.

Configuration Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Remote Analog Inputs

HMI Navigation Path: Settings Explorer, Analog Inputs

Configuration settings are made using the BE1-11 plugin for BESTCOMSPlus. To program the
configuration settings, use the Settings Explorer to open the Programmable Inputs, Remote Analog Inputs
tree branch and select the module and input to be modified. Refer to Figure 334. Use the drop-down
menu under Type to select the type of configuration. The analog inputs are always monitored and their
status is displayed on the appropriate metering screens. The BE1-11m reports Out of Range when an
RTD module is disconnected.

Ranges must be set for the selected input type. Param Min correlates to Min Input Current or Min Input
Voltage and Param Max correlates to Max Input Current or Max Input Voltage. Param Min and Param
Max are scaled values of the Min/Max Voltage/Current settings that are used for protection.

RTD Module

BE1-11m