9424200996 Rev L

397

Step 21: Navigate to Metering, Motor, Motor Meter on the front-panel display and verify that Thermal

Capacity is 0%.

Step 22: Apply 10 Aac three-phase current (simulate motor starting). Verify that OUT2 (Overloaded)

closes indicating an overloaded condition. Verify that the Starting LED is lit on the front panel.
Verify that the thermal capacity jumps from 0 to approximately 13% when current is applied and
then increases to 100%. Measure and record the time from when current is applied until OUT1
(Tripped) closes and the thermal capacity reaches 100%. The expected timing is 31.51 seconds
(87% of 36.22 seconds because %TC starts at 13%). Reference Equation 24. Verify that there
is a 49TC target on the front-panel display at Metering > Status > Targets.

Step 23: Remove three-phase current and wait until thermal capacity falls to 0% before proceeding.

Verify that the Stopped LED lights on the front panel. Reset all targets.

User Curve

Step 24: Use BESTCOMSPlus to send the operational settings in Table 176 to the BE1-11m. Reset all

targets.

Table 176. Operational Settings, User Curve

Setting

Value

BESTCOMSPlus Screen

Description

Nominal Frequency

60

System Parameters, Motor
Configuration

Sets Nominal Frequency
to 60 Hz

Nominal Secondary
Phase Voltage

69.3

System Parameters, Motor
Configuration

Sets Nominal Secondary
Phase Voltage to 69.3 V

Nominal Secondary
Phase Current CT1

5

System Parameters, Motor
Configuration

Sets Secondary Phase
Current CT1 to 5 A

Full Load Amps

2

System Parameters, Motor
Configuration

Sets Full Load Amps to 2

Service Factor

1

System Parameters, Motor
Configuration

Sets Service Factor to 1

Phase CT Ratio CT1

1

System Parameters, Sensing
Transformers

Sets Phase CT Ratio CT1
to 1

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets Phase CT Ratio CT1
to 1

Phase VT Connection

3W-D

System Parameters, Sensing
Transformers

Selects 3W-D Phase VT
Connection

Element Mode

User
Curve

Protection, Thermal, Thermal Curve
(49TC)

Selects User Curve mode

RTD Biasing

Disabled

Protection, Thermal, Thermal Curve
(49TC)

Disables RTD Biasing

Standard Curve Time
Dial

10

Protection, Thermal, Thermal Curve
(49TC)

Sets Standard Curve
Time Dial to 10

K

0

Protection, Thermal, Thermal Curve
(49TC)

Sets K to 0

Overload

1

Protection, Thermal, Thermal Curve
(49TC)

Sets Overload pickup to 1

Max Emergency
Thermal Capacity

0

Protection, Thermal, Thermal Curve
(49TC)

Sets Max Emergency
Thermal Capacity to 0%

Running Cool Time
Constant

1

Protection, Thermal, Thermal Curve
(49TC)

Sets Running Cool Time
Constant to 1 minute

Stopped Cool Time
Constant

1

Protection, Thermal, Thermal Curve
(49TC)

Sets Stopped Cool Time
Constant to 1 minute

BE1-11m

Thermal Curve (49TC) Test