One-shot/retriggerable mode – Basler Electric BE1-11m User Manual

Page 430

Advertising
background image

418

9424200996 Rev L

despite a second 43-1 OFF to ON initiate signal while the duration timer was active. Figure 279
illustrates the timing relationship of the 43-1 switch and 62-1 timer.

Figure 279. One-Shot/Non-Retriggerable Mode

Step 6: (Optional.) Repeat steps 1 through 5 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.

Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.

One-Shot/Retriggerable Mode

Step 1: Use BESTCOMSPlus to send the operational settings in Table 184 to the BE1-11m. Retain the

logic settings from Figure 276.

Table 184. Operational Settings (One-Shot/Retriggerable Mode)

Setting

Value

BESTCOMSPlus Screen

Description

62-1 Mode

One-
Shot/Retriggerable

Control, Logic Timers (62)

Sets 62-1 to One-
Shot/Retriggerable mode

62-1 Time
Delay 1 (T1)

15,000 ms

Control, Logic Timers (62)

Sets 62-1 pickup time delay to
15,000 ms

62-1 Time
Delay 2 (T2)

20,000 ms

Control, Logic Timers (62)

Sets 62-1 dropout time delay
to 20,000 ms

43-1 Mode

Pulse

Control, Virtual Control
Switches (43)

Sets 43-1 to Pulse mode

62-1 Target

Enabled

Target Configuration,
Targets screen.

Enables 62-1 target

Step 2: Step 4 supplies the 62-1 timer with a momentary initiate input by pulsing the 43-1 switch from

an OFF state to an ON state and then back to an OFF state. You can view the state changes of
the 43-1 switch at the Metering > Control > Virtual Switches screen on the front-panel display.

Step 3: Close communication with BESTCOMSPlus.

Step 4: Using the front-panel display, navigate to the Metering > Control > Virtual Switches screen.

Highlight the first switch (43-1) and press the Right key on the front panel to enter the 43-1
control screen. Use the Edit key to login. Highlight Operate and then press the Edit key to
change the state of the 43-1. Using the Up/Down keys select PUL and then press the Edit key.

Step 5: Repeat step 4.

Step 6: Wait at least 15 seconds (but no longer than 35 seconds) and then repeat step 4.

P

0

0

3

5

-3

1

0

2

-2

7

-0

6

Block

Initiate

62-x

Logic Timers (62) Test

BE1-11m