Inverse Overcurrent (51) Protection

Five inverse overcurrent (51) elements monitor the current applied to the BE1-11m. An element can be
configured to protect against overcurrent by monitoring a single- or three-phase system, neutral current,
positive-sequence current, negative-sequence current, ground current, or unbalanced current.

The five, identical inverse overcurrent protection elements are designated 51-1, 51-2, 51-3, 51-4, and 51-
5. Element logic connections are made on the BESTlogic

Plus screen in BESTCOMSPlus® and element

operational settings are configured on the Inverse Overcurrent settings screen in BESTCOMSPlus. A
summary of the logic inputs and outputs and operational settings appears at the end of this chapter.

BESTCOMSPlus Navigation Path: Settings Explorer, Protection, Current, Inverse Overcurrent (51)

HMI Navigation Path: Settings Explorer, Protection, Settings Group x (where x = 0 to 3), Current
Protection, Inverse Overcurrent 51

Element Operation

Inverse overcurrent protection can be used to protect equipment from damage caused by phase failure,
forward/reverse phase sequence, or phase unbalance.

Modes of Protection

Nine modes of protection are available: IA, IB, IC, Three-Phase, 3I0, I1, I2, IG, and Unbalance.

IA, IB, or IC Mode

The inverse overcurrent protection elements include three independent comparators, one for each phase.
Mode selection determines which phase pickup is required to activate protection.

Three-Phase Mode

The inverse overcurrent protection elements include three independent comparators, one for each phase.
Protection is activated when any of the three phases increases above the Pickup setting.

3I0 Mode

3I0 mode provides neutral overcurrent protection in a three-phase system.

I1 Mode

I1 mode provides positive-sequence overcurrent protection in a three-phase system.

I2 Mode

I2 mode provides negative-sequence overcurrent protection in a three-phase system. Refer to the

Negative-Sequence Overcurrent (46) Protection

chapter for more information.

IG Mode

IG mode provides ground fault protection in a three-phase system.

Unbalance Mode

Unbalance mode provides unbalanced current protection. Two methods are available to calculate
unbalanced current. The first method is based on the negative-sequence current divided by the positive-
sequence current while the second method is based on the average current. The calculation method must
be specified on the System Parameters, Sensing Transformers screen in BESTCOMSPlus. Refer to the

Configuration

chapter for more information.

BE1-11m

Inverse Overcurrent (51) Protection