General settings – Basler Electric BE1-11m User Manual

Page 530

Advertising
background image

518

9424200996 Rev L

General Settings

Display Units

Settings in this example are in metric and secondary units, based upon multiples of FLA (Full Load Amps)
and phase-to-phase voltages, unless otherwise specified. Phase-to-phase voltages are configured during
phase VT setup.

Use the Settings Explorer in BESTCOMSPlus

® to navigate to the General Settings, Display Units screen.

Select Metric for System Units and Secondary Units for Settings Display Modes, Thresholds. Refer to
Figure 340.

Figure 340. General Settings, Display Units Screen

Style Number

The BE1-11m style number shown in Figure 341 is used in this application example. The style number is
defined below.

Figure 341. BE1-11 Style Number

M ......... Application Option ...................... Motor

6 .......... Phase CT Option ........................ CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal

D .......... Ground CT Option ...................... CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal

1 .......... Power Supply Option ................. 48/125 Vac/dc

M ......... RS-485 Port Protocol ................. Modbus

1 .......... Ethernet Protocol ....................... BESTnet

Plus Only

J .......... Case Option ............................... Vertical Case

2 .......... Alarm Contact Option ................. Normally Closed (closes upon power removal / watchdog failure)

P .......... Option 1 ...................................... Phase Differential

0 .......... Network Connections ................. Copper

E .......... Language ................................... English

0 .......... Option 2 ...................................... None

00 ........ Firmware Option ......................... Latest Release

Settings Calculation Examples

BE1-11m