Basler Electric BE1-11m User Manual

Page 569

Advertising
background image

9424200996 Rev L

557

Equation 73. 2

nd

Slope (Starting) Pickup Setting

Figure 392 shows an example of 2

nd

Slope Restrained Operation.

Figure 392. 2

nd

Slope Restrained Operation Example

Based upon good engineering practices during starting mode to overcome dc offset and CT mismatches,
set Restraint Slope 2 % at 1.7 times the running mode slope and add a 25 percent margin. Restraint
Slope 2 % is calculated using Equation 74.

𝑅𝑒𝑠𝑡𝑟𝑎𝑖𝑛𝑡 𝑆𝑙𝑜𝑝𝑒 2 % = 𝐷𝐶 𝑂𝑓𝑓𝑠𝑒𝑡 ∙ 25% 𝑀𝑎𝑟𝑔𝑖𝑛 ∙ 𝑅𝑒𝑠𝑡𝑟𝑎𝑖𝑛𝑡 𝑀𝑜𝑑𝑒 1 % = 1.7 ∙ 1.25 ∙ 0.15% = 32%

Equation 74. Restraint Slope 2 %

Set the 2

nd

Slope Pickup (starting) at 3.42 and the Restraint Slope 2% at 32.

Alarm

The BE1-11m provides a Slope % alarm for cases where high loads or through faults cause unbalance in
the differential. The Slope % Alarm is calculated in Equation 75.

𝑆𝑙𝑜𝑝𝑒 % 𝐴𝑙𝑎𝑟𝑚 = 1.5 ∙ 𝑅𝑒𝑠𝑡𝑟𝑎𝑖𝑛𝑡 𝑆𝑙𝑜𝑝𝑒 2 % = 1.5 ∙ 32% = 48%

Equation 75. Slope % Alarm

The setting range for Slope % Alarm is 50 to 100 in increments of 1, so a Slope % Alarm of 50% is used
for this example.

The Current Differential (87) screen is shown in Figure 393.

BE1-11m

Settings Calculation Examples

Advertising