Figure 358 – Basler Electric BE1-11m User Manual

Page 543

Advertising
background image

9424200996 Rev L

531

Figure 358. 2

nd

Slope Restrained Operation Example

Alarm

The BE1-11m provides a Slope % alarm for cases where high loads or through faults cause unbalance in
the differential. The Slope % Alarm is calculated in Equation 52.

π‘†π‘™π‘œπ‘π‘’ % π΄π‘™π‘Žπ‘Ÿπ‘š = 1.5 βˆ™ π‘…π‘’π‘ π‘‘π‘Ÿπ‘Žπ‘–π‘›π‘‘ π‘†π‘™π‘œπ‘π‘’ 2 % = 1.5 βˆ™ 32% = 48%

Equation 52. Slope % Alarm

The setting range for Slope % Alarm is 50 to 100 in increments of 1, so a Slope % Alarm of 50% is used
for this example.

The Current Differential (87) screen is shown in Figure 359.

User Programmable Alarm 3 is used for reporting a minor alarm, which indicates a large percentage
restraint imbalance during starting mode. Use the Settings Explorer to navigate to Alarm Configuration,
User Programmable Alarms, and name User Programmable Alarm 3 to β€œDifferential Slope”. Navigate to
Alarm Configuration, Alarms, and enable Programmable Alarm 3 as a minor alarm. This alarm will show
up in the sequence of events and alarm reporting as β€œDifferential Slope”.

Figure 359. Protection, Current, Current Differential (87) Screen

BE1-11m

Settings Calculation Examples

Advertising