Logic Connections

Virtual control switch element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The virtual control switch element logic block is illustrated in Figure 78. Logic inputs
and outputs are summarized in Table 46.

Figure 78. Virtual Control Switch Element Logic Block

Table 46. Logic Inputs and Outputs

Name

Logic Function

Purpose

Set

Input

Sets the state of the output to true

Reset

Input

Sets the state of the output to false

Pulse

Input

Momentarily changes state of the output

Informational Tag

Input

Sets an informational tag on the 43 element

Informational Untag

Input

Removes the informational tag from the 43 element

Blocking Tag

Input

Sets a blocking tag on the 43 element

Blocking Untag

Input

Removes the blocking tag from the 43 element

Output

Output

True when the 43 element is set

Operational Settings

Virtual control switch element operational settings are configured on the Virtual Control Switches (43)
settings screen (Figure 79) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 47.

BE1-11m

Virtual Control Switches (43)