182

9424200996 Rev L

Voltage

Figure 144 illustrates the Power Quality, Voltage screen.

Figure 144. Power Quality, Voltage Screen

10-Second Frequency

A 10-second average of the frequency is calculated using Equation 20.

π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ πΌπ‘›π‘‘π‘’π‘”π‘Ÿπ‘Žπ‘™ 𝐢𝑦𝑐𝑙𝑒𝑠

π‘‡π‘œπ‘‘π‘Žπ‘™ π·π‘’π‘Ÿπ‘Žπ‘‘π‘–π‘œπ‘› π‘œπ‘“ πΌπ‘›π‘‘π‘’π‘”π‘’π‘Ÿ 𝐢𝑦𝑐𝑙𝑒𝑠

Equation 20. 10-Second Frequency Calculation

Example

Number of integral cycles: 501 cycles over 10 s

Total duration of the 501 cycles: 9.998 s

10-Second Frequency = 501/9.998 = 50.1100 Hz

Distortion

The voltage during a dip is often distorted. This distortion may be important for understanding the effect of
the dip on the system. The BE1-11m calculates distortion using Equation 21.

οΏ½

𝑉

π‘‡π‘œπ‘‘π‘Žπ‘™

𝑉

πΉπ‘’π‘›π‘‘π‘Žπ‘šπ‘’π‘›π‘‘π‘Žπ‘™

βˆ’ 1οΏ½ Γ— 100

Equation 21. Distortion Calculation

Figure 145 illustrates the Power Quality, Distortion screen.

Figure 145. Power Quality, Distortion Screen

Dip/Swell

Figure 146 illustrates the Power Quality, Dip/Swell screen. A green LED indicates that the threshold
specified in Power Quality Settings has been exceeded.