Sensing transformers settings, Ct setup – Basler Electric BE1-11m User Manual

Page 298

Advertising
background image

286

9424200996 Rev L

Setting

Range

Increment

Unit

Default

Nominal Aux
Voltage

50 to 300

0.01

volts

69.3

Power Polarity

Normal or Reverse

n/a

n/a

Normal

Phase Rotation

ABC or ACB

n/a

n/a

ABC

Full Load Amps

1 to 25 (%A CTs)
0.2 to 5 (1A CTs)

0.001

amps

1

Service Factor

1 to 1.4

0.01

units

1

Motor Start
Detection

Current Only, Current and Contacts, or

Contacts Only

n/a

n/a

Current

Only

Motor Stop
Detection

Current Only, Current and Contacts, or

Contacts Only

n/a

n/a

Current

Only

Sensing Transformers Settings

The BE1-11m requires information about the current and voltage transformers to provide metering, fault
reporting, and protective relaying.

Sensing transformer settings are configured on the Sensing Transformers settings screen in
BESTCOMSPlus. A summary of the settings appear at the end of this section.

BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Sensing Transformers

HMI Navigation Path: Settings Explorer, System Parameters, Sensing Transformers

CT Setup

The BE1-11m requires setting information on the CT ratios. This setting is used by the metering and fault
reporting functions to display measured quantities in primary units.

Unbalanced Calculation Method

Unbalanced overcurrent protection is provided by the 50 and 51 elements. Two methods are available to
calculate unbalanced current.

Method 1 (I2/I1)

𝐼

π‘ˆπ‘›π‘π‘Žπ‘™π‘Žπ‘›π‘π‘’

=

𝐼

2

𝐼

1

Γ— MIN

where:

MIN =

𝐼

π΄π‘£π‘’π‘Ÿπ‘Žπ‘”π‘’

𝐼

π‘…π‘Žπ‘‘π‘’π‘‘

or 1, whichever is less

Method 2 (Average)

𝐼

π‘ˆπ‘›π‘π‘Žπ‘™π‘Žπ‘›π‘π‘’

=

οΏ½MAXp βˆ’ I

π΄π‘£π‘’π‘Ÿπ‘Žπ‘”π‘’

οΏ½ or οΏ½I

π΄π‘£π‘’π‘Ÿπ‘Žπ‘”π‘’

βˆ’ MINpοΏ½, whichever is greater

I

π΄π‘£π‘’π‘Ÿπ‘Žπ‘”π‘’

Γ— MIN

where:

MIN =

𝐼

π΄π‘£π‘’π‘Ÿπ‘Žπ‘”π‘’

𝐼

π‘…π‘Žπ‘‘π‘’π‘‘

or 1, whichever is less

MAXp = maximum of all three phases
MINp = minimum of all three phases

Configuration

BE1-11m