Figure 319. External Three-Wire RTD Input Connections

RTD Module Communications Setup Procedure

Communication between the BE1-11m and the RTD module can be accomplished via Ethernet or
RS-485. Initial settings for the RTD module must be made via Ethernet.

An IP address is assigned to the RTD module in all cases even if the connection between the RTD
module and the BE1-11m will be RS-485. Assigning an IP address to the RTD module gives the user the
option to save a settings file and to view the serial number and firmware version of the RTD module using
BESTCOMSPlus.

Perform one of the following procedures to set up the RTD module.

Procedure 1

The PC and BE1-11m are connected through a network or the PC is connected directly to the BE1-11m
via Ethernet cable or USB cable. The RTD module connects to the BE1-11m via Ethernet or RS-485. See
Figure 320.

Figure 320. Procedure 1

Connect to RTD Module

1.

Connect an Ethernet cable directly between the PC and RTD module.

2.

Apply operating power to the RTD module.

3.

Determine the IP address, Subnet Mask, and Default Gateway of the PC Ethernet port for later use.
Open a Windows

® command prompt by clicking Start  Run. Type “cmd”, and click OK. Type

“ipconfig” and press enter.

4.

Record the IP address, Subnet Mask, and Default Gateway of the PC Ethernet port that is connected
to the RTD module. Close the Windows command prompt window.

RTD1+

RTD1–

RTD1C

RTD Module

P

0

0

6

1

-4

1

RED

BLACK

BLACK

N

e

t

w

o

r

k

PC

BE1-11m

RTD Module

Ethernet

Ethernet

P

0

0

6

1

-8

5

RS-485

Ethernet

= Optional

OR

PC

BE1-11m

RTD Module

Ethernet

USB

RTD Module

BE1-11m