Retrieving lockout status from the be1-11m, N table 51 – Basler Electric BE1-11m User Manual

Page 136

Advertising
background image

124

9424200996 Rev L

Table 51. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Retrieving Lockout Status from the BE1-11m

Lockout status can be viewed through BESTCOMSPlus, the front-panel display, and the web page
interface.

To view 86 lockout status using BESTCOMSPlus, use the Metering Explorer to open the Status, 86
Lockout Status screen shown in Figure 90. To view lockout status from the front-panel display, navigate
to Metering Explorer, Status, 86 Lockout Status.

Figure 90. 86 Lockout Status Screen

Lockout Functions (86)

BE1-11m