50BF - Breaker Failure Protection

Phase & Ground Pickup
5 Ampere CT Setting Range ..................................... 0.25 to 10 A
1 Ampere CT Setting Range ..................................... 0.05 to 2 A
SEF ........................................................................... 0.01 to 0.5 A

Accuracy

5 Ampere CT .............................................................

±4% or ±50 mA, whichever is greater

1 Ampere CT .............................................................

±4% or ±10 mA, whichever is greater

SEF ...........................................................................

±(5% + 2.5 mA)

Time Delay & Control Time
Setting Range ........................................................... 50 to 999 ms
Accuracy....................................................................

±1% or +3, –0.5 cycles, whichever is greater

51 - Inverse Overcurrent Protection

Pickup
5 Ampere CT Setting Range ..................................... 0.5 to 16 A
1 Ampere CT Setting Range ..................................... 0.1 to 3.2 A
SEF Setting Range ................................................... 0.01 to 0.8 A
Unbalanced Setting Range ....................................... 2 to 100%
Dropout ..................................................................... 93 to 99% of the actual pickup value

3Phase, IA, IB, IC, IG Accuracy

5 Ampere CT .............................................................

±4% or ±50 mA, whichever is greater

1 Ampere CT .............................................................

±4% or ±10 mA, whichever is greater

SEF ...........................................................................

±(5% + 2.5 mA)

3I0, I1, I2 Accuracy

5 Ampere CT .............................................................

±3% or ±75 mA, whichever is greater

1 Ampere CT .............................................................

±3% or ±15 mA, whichever is greater

Unbalanced Accuracy

5 Ampere CT .............................................................

±3% of pickup setting

1 Ampere CT .............................................................

±3% of pickup setting

Time Current Characteristic Curves

Timing Accuracy (All 51 Functions) ..........................

±8% or ±4 cycles, whichever is greater, for time dial

settings greater than 0.1 and multiples of 2 to 40
times the pickup setting but not over 150 A for 5 A
CT units or 30 A for 1 A CT units.
Refer to the

Time Curve Characteristics

chapter

for information on available timing curves.

Voltage Restraint
Control/Restraint Range ............................................ 30 to 250 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

55 - Power Factor Protection

Lagging/Leading Pickup
Setting Range ........................................................... 0.05 to 0.99
Accuracy....................................................................

±0.02

Time Delay
Setting Range ........................................................... 50 to 60,000 ms
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

BE1-11m

Specifications - 25 Hz Operation