Functional test report, Pickup verification table 2 row 1, Pickup verification table 2 row 2 – Basler Electric BE1-11m User Manual

Page 401: Pickup verification table 2 row 3

Advertising
background image

9424200996 Rev L

389

Step 3: Connect and apply 5A

∠0° to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity) and

a three-phase 69.28 V phase-neutral voltage source to terminals C13 (A-phase), C14 (B-
phase), C15 (C-phase), and C16 (Neutral).

Step 4: Rotate the IA angle in the leading or lagging direction until a pickup occurs. This should occur at

60,000ms

± 300ms. Decrease the IA angle until OUT1 opens. Reset the target. Measure the

time delay and record the result.

Step 5:

Repeat step 4 for the time delays in the second and third rows of Table 2. Record the results.
Timing accuracy is

±0.5% or 2 cycles, whichever is greater.

Step 6: (Optional.) Repeat steps 1 through 5 for the B-phase and C-phase voltage inputs taking into

consideration the different current angles. Note: Be sure to enable proper target for each phase
being tested.

Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.

Functional Test Report

Pickup Verification Table 2 Row 1

Pickup Setting Range = 0.05 to 0.99 leading/lagging

Pickup Accuracy =

±0.01

Step

Pickup Setting

Low

Actual

Pickup

High

Pass/Fail

6-IA

+60

° (0.5 leading)

59.34

°

60.66

°

P / F

7-IA

–60° (0.5 lagging)

–59.34°

–60.66°

P / F

6-IB

+300

° (0.5 leading)

299.34

°

300.66

°

P / F

7-IB

+180

° (0.5 lagging)

179.34

°

180.66

°

P / F

6-IC

+180

° (0.5 leading)

179.34

°

180.66

°

P / F

7-IC

+60

° (0.5 lagging)

59.34

°

60.66

°

P / F

Pickup Verification Table 2 Row 2

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

6-IA

+87.1

° (0.05 leading)

86.56

°

87.71

°

P / F

7-IA

–8.1° (0.99 lagging)

–11.48°

0

°

P / F

6-IB

+327.1

° (0.05 leading)

326.56

°

327.71

°

P / F

7-IB

+231.8

° (0.99 lagging)

228.52

°

231.89

°

P / F

6-IC

+207.1

° (0.05 leading)

206.56

°

207.71

°

P / F

7-IC

+111.8

° (0.99 lagging)

108.52

°

120

°

P / F

Pickup Verification Table 2 Row 3

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

6-IA

+8.1

° (0.99 leading)

0

°

11.48

°

P / F

7-IA

–87.1° (0.05 lagging)

–87.71°

–86.56°

P / F

6-IB

+248.1

° (0.99 leading)

240

°

251.48

°

P / F

7-IB

+152.9

° (0.05 lagging)

152.29

°

153.44

°

P / F

6-IC

+128.1

° (0.99 leading)

120

°

131.48

°

P / F

7-IC

+32.9

° (0.05 lagging)

32.29

°

33.44

°

P / F

BE1-11m

Power Factor (55) Test