Timing verification (v1 mode), Pickup verification (v2 mode), N table 110 – Basler Electric BE1-11m User Manual

Page 330

Advertising
background image

318

9424200996 Rev L

Table 110. Pickup Test Settings (V1 Mode)

Pickup Setting

Time Delay

82 V

50 ms

42 V

50 ms

25 V

50 ms

Step 4: Prepare to monitor the 59X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 244).

Step 5: Connect and apply a 240 Vac, single-phase voltage source to terminals C13 (A-phase) and C16

(neutral). For a single-phase input test, V1 = A-phase voltage / 3. Therefore, the BE1-11m
should pick up at a value of three times the setting value when applying only a single-phase
input. For example, to determine the pickup voltage value required for a BE1-11m with a pickup
setting of 82, it would require 82 times 3 or 246 volts of input voltage.

Step 6: Slowly increase the voltage until OUT2 closes and record the pickup. Verify that there is a 59X-

1-V1 target on the front-panel display. Slowly decrease the voltage until OUT2 opens and
record the dropout. Reset the target.

Step 7: Verify the pickup and dropout accuracy at 120 Vac for a pickup setting of 42 V (126 Vac on test

set) and 70 Vac for a pickup setting of 25 V (75 Vac on test set) as listed in Table 110. Record
the results.

Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 59X-2.

Timing Verification (V1 Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 111 to the BE1-11m for settings group 0.

Table 111. Timing Test Settings (V1 Mode)

Pickup Setting

Time Delay

42 V

2,000 ms

42 V

5,000 ms

42 V

10,000 ms

Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed

time between a sensing voltage change and OUT1 closing.

Step 3: Connect and apply a 120 Vac, single-phase voltage source to terminals C13 (A-phase) and C16

(neutral).

Step 4: Step the voltage up to 130 volts. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 111. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 59X-2.

Pickup Verification (V2 Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 112 to the BE1-11m. Reset all

targets.

Auxiliary Overvoltage (59X) Test

BE1-11m