Operational settings, Figure 93, N table 52 – Basler Electric BE1-11m User Manual

Page 139

Advertising
background image

9424200996 Rev L

127

Figure 93. Breaker Control Element Logic Block

Table 52. Logic Inputs and Outputs

Name

Logic Function

Purpose

Trip

Input

Sets the state of the 101 element to Trip

Close

Input

Sets the state of the 101 element to Close

Informational Tag

Input

Sets an informational tag on the 101 element

Informational Untag

Input

Removes the informational tag from the 101 element

Blocking Tag

Input

Sets a blocking tag on the 101 element

Blocking Untag

Input

Removes the blocking tag from the 101 element

Trip

Output

True if the 101 element is in the Trip state

TSC

Output

True after the Trip output momentarily closes

Close

Output

True if the 101 element is in the Close state

CSC

Output

True after the Close output momentarily closes

Operational Settings

Breaker control element operational settings are configured on the Breaker Control Switch (101) settings
screen (Figure 94) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 53.

Figure 94. Breaker Control Switch Settings Screen

Table 53. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

BE1-11m

Breaker Control Switch (101)

Advertising