Operational settings, Table 14 – Basler Electric BE1-11m User Manual

Page 64

Advertising
background image

52

9424200996 Rev L

Table 14. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 81 function when true

Trip

Output

True when the 81 element is in a trip condition

Pickup

Output

True when the 81 element is in a pickup condition

Operational Settings

Frequency element operational settings are configured on the Frequency settings screen (Figure 39) in
BESTCOMSPlus. Setting ranges and defaults are summarized in Table 15.

Figure 39. Frequency Settings Screen

Table 15. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

Mode

Disabled, Over, Under,

Rate of Change,

Positive Rate of Change,

or Negative Rate of Change

n/a

n/a

Disabled

Pickup

0 or 0.2 to 20 for ROC mode

0 or 15 to 70 for O/U mode

0.01

hertz/sec (ROC)

hertz (O/U)

0

Time Delay

0 to 600,000

varies

milliseconds

0

Voltage Inhibit

0 or 15 to 250

0.1

volts

*

20

81ROC

Over Frequency Inhibit

15 to 70 Hz

0.01

hertz

61

Under Frequency Inhibit

15 to 70 Hz

0.01

hertz

59

Negative Sequence

Inhibit

0 to 99

1

percent

20

* Phase-to-phase and phase-to-neutral settings depend on the Phase VT and Aux VT connection
settings. Refer to the

Configuration

chapter for more information on these settings.

Frequency (81) Protection

BE1-11m

Advertising