Output contacts, Contact-sensing inputs – Basler Electric BE1-11m User Manual

Page 456

Advertising
background image

444

9424200996 Rev L

Option 2 (125/250 Vac/dc)
DC Operating Range ................................................. 90 to 300 Vdc
AC Operating Range ................................................. 90 to 270 Vac

Option 3 (24 Vdc)
Operating Range ....................................................... 17 to 32 Vdc (down to 8 Vdc momentarily)

Frequency Range
Options 1 and 2 only ................................................. 40 to 70 Hz

Burden
Options 1, 2, and 3 .................................................... 12 W continuous, 14 W maximum with all outputs

energized

Output Contacts

Make and Carry for Tripping Duty ............................. 30 A for 0.2 seconds per IEEE Std C37.90-2005 -

IEEE Standard for Relays and Relay Systems
Associated with Electric Power Apparatus
;

7 A continuous AC or DC

Break Resistive or Inductive ...................................... 0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)

Terminals
OUT 1 ........................................................................ C1, C2
OUT 2 ........................................................................ C3, C4
OUT 3 ........................................................................ C5, C6
OUT 4 ........................................................................ C7, C8
OUT 5 ........................................................................ C9, C10
OUT 6 ........................................................................ E11, E12
OUT 7 ........................................................................ E9, E10
OUT 8 ........................................................................ E7, E8
OUT A ....................................................................... C11, C12

Contact-Sensing Inputs

Maximum Input Voltage

The maximum input voltages are the highest voltage for each power-supply range listed under the Power
Supply
section.

Turn-On Voltage

Contact-sensing turn-on voltages are listed in Table 190.

Table 190. Contact-Sensing Turn-On Voltages

Style Option

Nominal Input Voltage

Contact-Sensing Turn-On Voltage

*

Jumper Installed

(Low Position) †

Jumper Not Installed

(High Position) †

Mxx1xxxxxxxxxx

48 Vdc or 125 Vac/dc

26 to 38 Vdc

69 to 100 Vdc

56 to 97 Vac

Mxx2xxxxxxxxxx

125/250 Vac/dc

69 to 100 Vdc

56 to 97 Vac

138 to 200 Vdc
112 to 194 Vac

Mxx3xxxxxxxxxx

24 Vdc

n/a

Approx. 5 Vdc

* AC voltage ranges are calculated using the default recognition time (4 ms) and debounce time (4 ms).

† Voltage ranges depend on jumper configurations. See the

Contact Inputs and Outputs

chapter for more

information.

Specifications

BE1-11m