Protection - incomplete sequence (48) – Basler Electric BE1-11m User Manual

Page 576

Advertising
background image

564

9424200996 Rev L

Figure 400. Protection, Frequency Screen

Overfrequency (81-2)

The 81-2 protection element alarms when the source frequency is 5 percent above nominal. A time delay
of 100 ms is used to avoid nuisance alarms. The pickup setting is calculated in Equation 83.

π‘ƒπ‘–π‘π‘˜π‘’π‘ = (100 + 5%) βˆ™ π‘π‘œπ‘šπ‘–π‘›π‘Žπ‘™ πΉπ‘Ÿπ‘’π‘žπ‘’π‘’π‘›π‘π‘¦ = 1.05 βˆ™ 60 = 63 𝐻𝑧

Equation 83. 81-2 Pickup

Select Over mode, set the Pickup setting to 63 Hz, and set the Time Delay to 100 ms as shown in Figure
400.

Protection - Incomplete Sequence (48)

The 48 protection element is used as backup protection to the 49TC and 50 elements. The incomplete
sequence protection element monitors the starting time and returns the motor to the off state if the starting
sequence is not completed within a predetermined time. Motor start and motor run status is provided to
the 48 element from the motor status logic element in BESTlogicPlus. For an incomplete start, the 48
element times out based on the time it takes the motor to drop below the starting mode condition. One or
two seconds should be added after the nominal start time to trip the motor. The time interval is calculated
in Equation 84.

π‘‡π‘–π‘šπ‘’ πΌπ‘›π‘‘π‘’π‘Ÿπ‘£π‘Žπ‘™ = π‘‡π‘–π‘šπ‘’

π‘†π‘‘π‘Žπ‘Ÿπ‘‘

+ 2 𝑠 = 2.42 𝑠 + 2 𝑠 = 4.42 𝑠

Equation 84. 48 Time Interval

Enable the 48 element and set the Time Interval to 4.42 seconds as shown in Figure 401.

Settings Calculation Examples

BE1-11m

Advertising