Restart inhibit protection, Automatic setting group characteristics, Bestlogic™plus – Basler Electric BE1-11m User Manual

Page 454: General specifications, Ac current inputs

Advertising
background image

442

9424200996 Rev L

Restraint Slope 1
Setting Range ........................................................... 5 to 100%

Restraint Slope 2
Setting Range ........................................................... 15 to 140%

Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................

±0.5% or ±½ cycle, whichever is greater, plus trip

time for instantaneous response (0.0 setting)

*

* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup

setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.

Restart Inhibit Protection

Restart Delay
Setting Range ........................................................... 0 to 7,200 min
Accuracy....................................................................

±0.5% or ±3 cycles

Time Between Starts
Setting Range ........................................................... 0 to 7,200 min
Accuracy....................................................................

±0.5% or ±3 cycles

Automatic Setting Group Characteristics

Number of Setting Groups ........................................ 4

Control Modes
Automatic .................................................................. Cold-Load Pickup, Dynamic Load or Unbalance
External ..................................................................... Discrete Input Logic, Binary Input Logic

Switch Threshold
Range ........................................................................ 0.1 to 25 A (5 A), 0.02 to 5 A (1 A)
Accuracy....................................................................

±2% or ±0.05 A (5 A), ±2% or ±0.01 A (1 A)

Switch Time
Range ........................................................................ 0 to 60 min with 1 min increments where 0 =

disabled

Accuracy....................................................................

±0.5% or ±2 s, whichever is greater

BESTlogic

Plus

Update Rate .............................................................. ¼ cycle

General Specifications

AC Current Inputs

5 Ampere CT
Continuous Rating ..................................................... 20 A
One Second Rating ................................................... 400 A

For other current levels, use the formula: I= (K/t)

½

where t = time in seconds, K = 160,000.

Begins to Clip (Saturate) ........................................... 150 A
Burden ....................................................................... <10 m

Specifications

BE1-11m

Advertising