Time overcurrent characteristic curve graphs – Basler Electric BE1-11m User Manual

Page 472

Advertising
background image

460

9424200996 Rev L

Curve

Selection

Curve Name

Trip Characteristic Constants

Reset

A

B

C

N

K

R

A1

IEC Inverse

0.14

0

1

0.02

0

20

I1

CO Inverse Time

8.9341

0.17966

1

2.0938

0.028

9

I2

IAC Inverse Time

0.2747

0.10426

1

0.4375

0.028

0.8868

M

CO Moderately Inverse

0.3022

0.1284

1

0.5

0.028

1.75

D1

IEEE Moderately Inverse

0.0515

0.114

1

0.02

0

4.85

L1

CO Long Inverse

5.6143

2.18592

1

1

0.028

15.75

L2

IAC Long Inverse

2.3955

0

1

0.3125

0.028

7.8001

G

Long Time Inverse (I

2

t)

12.1212

0

1

1

0.028

29

V1

CO Very Inverse

5.4678

0.10814

1

2.0469

0.028

5.5

V2

IAC Very Inverse

4.4309

0.0991

1

1.9531

0.028

5.8231

B

Very Inverse (I

2

t)

1.4636

0

1

1.0469

0.028

3.25

B1

IEC Very Inverse

13.5

0

1

1

0

30.6

E3

IEEE Very Inverse

19.61

0.491

1

2

0

21.6

E1

CO Extremely Inverse

7.7624

0.02758

1

2.0938

0.028

7.75

E2

IAC Extremely Inverse

4.9883

0.0129

1

2.0469

0.028

4.7742

C

Extremely Inverse (I

2

t)

8.2506

0

1

2.0469

0.028

8

C1

IEC Extremely Inverse

80

0

1

2

0

77.6

F1

IEEE Extremely Inverse

28.2

0.1217

1

2

0

29.1

D

CO Definite Time

0.4797

0.21359

1

1.5625

0.028

0.875

F

Fixed Time ‡

0

1

0

0

0

1

46

K Factor

0

0

2

0.028

100

P

User Programmable §

0 to 600

0 to 25

0 to 1

0.5 to 2.5

0.028

0 to 30

T1

User Table 1

n/a

n/a

n/a

n/a

n/a

n/a

T2

User Table 2

n/a

n/a

n/a

n/a

n/a

n/a

T3

User Table 3

n/a

n/a

n/a

n/a

n/a

n/a

T4

User Table 4

n/a

n/a

n/a

n/a

n/a

n/a

∗ Instantaneous or integrating reset is selected on the Inverse Overcurrent setup screen in

BESTCOMSPlus

®.

† Constant A is variable for the 46 curve and is determined, as necessary, based on system full-load

current setting, minimum pickup, and K factor settings.

‡ Curve F has a fixed delay of one second times the Time Dial setting.

§ The programmable curve allows for four significant digits after the decimal place for every variable.

║ There is a minimum of 2 and maximum of 40 points that can be entered for any one T curve. For

information on setting T curves, refer to the

Inverse Overcurrent (51) Protection

chapter.

Time Overcurrent Characteristic Curve Graphs

The figures after the tables illustrate the characteristic curves of the BE1-11m. Table 193 cross-references
each curve to existing electromechanical relay characteristics. Equivalent time dial settings were
calculated at a value of five times pickup.

Time Curve Characteristics