Timing verification (3v0 mode) – Basler Electric BE1-11m User Manual

Page 328

Advertising
background image

316

9424200996 Rev L

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 243.

Blocking is disabled.

OUT1 closes for 59X-1 Trip.

OUT2 closes for 59X-1 Pickup.

Fault recording is enabled.

Figure 243. BESTlogicPlus Settings (3V0 Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 107 to the BE1-11m.

Table 107. Pickup Test Settings (3V0 Mode)

Pickup Setting

Time Delay

115 V

50 ms

65 V

50 ms

20 V

50 ms

Step 4: Prepare to monitor the 59X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 243).

Step 5: Connect and apply a 150 Vac, three-phase voltage source to terminals C13 (A-phase), C14 (B-

phase), C15 (C-phase), and C16 (neutral).

Step 6: Slowly increase the A-phase voltage until OUT2 closes around 265 volts (150 Vac nominal +

115 V 3V0 pickup setting) and record the pickup. Verify that there is a 59X-1-3V0 target on the
front-panel display. Slowly decrease the A-phase voltage until OUT2 opens and record the
dropout. Reset the target.

Step 7: Verify the pickup and dropout accuracy at a pickup setting of 65 V and 20 V as listed in Table

107. Record the results.

Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 59X-2.

Timing Verification (3V0 Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 108 to the BE1-11m for settings group 0.

Table 108. Timing Test Settings (3V0 Mode)

Pickup Setting

Time Delay

65 V

2,000 ms

65 V

5,000 ms

65 V

10,000 ms

Auxiliary Overvoltage (59X) Test

BE1-11m