9424200996 Rev L

77

Figure 53. Phase Current Differential Settings Screen

Figure 54. Phase Current Differential Operation Chart

Table 28. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

87 Mode

Disabled, Percent Differential, or

Flux Balance

n/a

n/a

Disabled

Slope Mode

Maximum or Average

n/a

n/a

Maximum

Minimum Restrained

Pickup

0 or 0.1 to 1

0.01

n/a

0

Restraint Slope 1

5 to 100

1

percent

45

Flux Balance Pickup

0 or 0.1 to 5

0.01

amps

0

Time Delay

0 to 60,000

varies

milliseconds

0

BE1-11m

Phase Current Differential (87) Protection