9424200996 Rev L

71

Figure 49. 51 Phase Pickup Level Compensation

π΄π‘π‘‘π‘’π‘Žπ‘™ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝐿𝑒𝑣𝑒𝑙 =

𝑆𝑒𝑛𝑠𝑖𝑛𝑔 π‘‰π‘œπ‘™π‘‘π‘Žπ‘”π‘’ 𝐿𝑒𝑣𝑒𝑙

π‘…π‘’π‘ π‘‘π‘Ÿπ‘Žπ‘–π‘›π‘‘ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝑆𝑒𝑑𝑑𝑖𝑛𝑔 Γ— 51 π‘ƒβ„Žπ‘Žπ‘ π‘’ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝑆𝑒𝑑𝑑𝑖𝑛𝑔

Equation 3. Restraint Pickup Level

Phase VT Configuration

The 51/27R function can be set to monitor either Vpp or Vpn depending upon the Phase VT Connection
settings. See the

Configuration

chapter for details on how to set the phase VT connections. Table 24

shows which voltage measurements are used by each 51 element for each possible phase VT connection
and 51/27 voltage monitoring mode setting.

Table 24. Phase VT Connection Cross Reference

Phase VT Connection

51/27 Mode

51A

51B

51C

4W

Vpp

Vab

Vbc

Vca

4W

Vpn

Van

Vbn

Vcn

3W

Vpp

Vab

Vbc

Vca

AN

Vpn

Van

n/a

n/a

BN

Vpn

n/a

Vbn

n/a

CN

Vpn

n/a

n/a

Vcn

AB

Vpp

Vab

n/a

n/a

BC

Vpp

n/a

Vbc

n/a

CA

Vpp

n/a

n/a

Vca

Note

For single-phase sensing, the unmonitored phase is not restrained or
controlled. These phases are marked in the table by n/a (not
applicable).

When single-phase voltage sensing is used, only the inverse overcurrent element on the phase with
voltage magnitude information is affected by the 51/27R feature. Thus, in voltage control mode, the 51
elements on the two unmonitored phases will always be disabled. In voltage restraint mode, the 51
elements on the two unmonitored phases will not have their overcurrent pickup settings adjusted from
100%.

BE1-11m

Inverse Overcurrent (51) Protection