Troubleshooting, Communications, Ethernet port does not operate properly – Basler Electric BE1-11m User Manual

Page 443: Usb port does not operate properly

Advertising
background image

9424200996 Rev L

431

Troubleshooting

Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or
solid-state component relays. Both must be wired together with inputs and outputs, and have operating
settings applied. Logic settings determine which protection elements are electronically wired to the inputs
and outputs of the device. Operating settings determine the pickup thresholds and time delays.

The logic and operating settings should be tested by applying actual inputs and operating quantities and
verifying proper output response. For more details, refer to the testing chapters. All of the following
connections and functions should be verified during commissioning tests:

Proper connection and sensing of current and voltage signals

Input and output contact connections

I/O sensing

Settings validation

Proper operation of equipment (main or auxiliary)

Proper alarming (to SCADA) and/or targeting

If you do not get the results that you expect from the BE1-11m, first check the programmable settings for
the appropriate function. Use the following troubleshooting procedures when difficulties are encountered
in the operation of your BE1-11m.

Warning!

Troubleshooting of the BE1-11m should be performed only by qualified
personnel. High voltage may be present on the rear terminals of the
BE1-11m.

Communications

Ethernet Port Does Not Operate Properly

Step 1. Verify that the proper port of your computer is being used. For more information, refer to the

Communication

chapter.

Step 2. Verify that the network configuration of the BE1-11m is set up properly. For more information,

refer to the

Communication

chapter.

USB Port Does Not Operate Properly

Verify that the USB driver was installed properly. For more information, refer to the

BESTCOMSPlus

Software

chapter.

Why do I keep getting access conflict errors when I attempt communication with the
BE1-11m
?

If you try to gain access to more than one port at a time, an access conflict results. The BE1-11m has
three communication ports: front-panel USB, rear panel optional Ethernet, and rear panel RS-485. Each
communication method has its own access. For example, if you gain access through Modbus TCP, then
you cannot gain access using BESTCOMSPlus over Ethernet. Access needs to be gained only when a
write command to the BE1-11m is required (control or setting change or report reset).

When access is gained through a port, a user-defined access control timer starts counting down to zero.
When port activity occurs, the timer resets to the user-defined access control timer setting and resumes
counting down. If no activity is seen for the duration of the access control timer setting, access is

BE1-11m